Siemens FS-TRI-M Installation Instructions
Siemens FS-TRI-M Installation Instructions

Siemens FS-TRI-M Installation Instructions

Contact monitoring module

Advertisement

Quick Links

Installation Instructions
Models FS-TRI-M
Contact Monitoring Module
The SIEMENS FS-TRI-M Contact Monitoring Module,
as shown in Figure 1, interfaces normally open contact
devices to an Addressable Device Circuit of a fire
alarm control unit.
The FS-TRI-M supports Style B (Class B) Initiating
Device Circuit wiring. Each module uses one address
on the Addressable Device Circuit. It does not require
any mechanical address programming. Use the FS-FPI
Programmer/Tester to program and test the module.
PROGRAMMING INSTRUCTIONS
CAUTION:
1. To prevent damage to the FS-FPI, do not
connect modules to the FS-FPI until the
Addressable Device Circuit wiring is
disconnected.
2. Only one device must be connected to the
FS-FPI at a time.
1. Connect the red and black wires of the FS-TRI-M
to the SIEMENS FS-FPI Programmer/Tester. Use
the cable provided with the Programmer/Tester
and the 2 alligator clips provided.
Figure 1
FS-TRI-M Module
Siemens Building Technologies, Inc.
8 Fernwood Road
Florham Park, New Jersey 07932
P/N 315-699487-1
2. Set the address for the module by following the
instructions in the FS-FPI Programmer/Tester
Manual (P/N 315-699480).
3. Record the device address on the label located
on the module. The module can now be installed
and wired to the system.
MOUNTING
The FS-TRI-M must be installed in a
UL Listed electrical box.
Refer to Figure 2.
1. Connect the appropriate wires using wire nuts.
Tuck the FS-TRI-M module inside the electrical
box and dress the wiring as required.
2. Fasten the cover plate (user supplied) to the box.
SINGLE GANG
SWITCHPLATE (BLANK)
(USER SUPPLIED)
Figure 2
FS-TRI-M Mounting
Siemens Building Technologies, Ltd.
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 CN
Fire Safety
NOTE:
DO NOT USE
REAR CONDUIT ENTRY
FS-TRI-M
SINGLE GANG
SWITCHBOX
(USER SUPPLIED)

Advertisement

loading

Summary of Contents for Siemens FS-TRI-M

  • Page 1 2. Only one device must be connected to the FS-FPI at a time. 1. Connect the red and black wires of the FS-TRI-M to the SIEMENS FS-FPI Programmer/Tester. Use the cable provided with the Programmer/Tester and the 2 alligator clips provided.
  • Page 2 Figure 3 FS-TRI-M Wiring NOTES: 1. All circuits are power limited. 2. In supervisory: FS-TRI-M draws 1.5mA 3. Initiating Device Circuit ratings: Style B, Class B See NFPA 72 standard for the number of normally open contact devices allowed. Voltage (max.): 5 VDC (during polling) Supervisory current (max.):...