User Instructions

8.1
Commissioning and hand over
Warning
As part of the commissioning programme, the
commissioning engineer must go through the following with
the operator.
(i) Lighting, shutdown, and operational information.
(ii) Safety features, data plate, and labelling.
(iii) The requirement for regular inspection - especially if the
heater is within a more demanding environment - and the
need for regular servicing, carried out by competent and
qualified engineers.
Caution
After approximately 100 hours of running, the tension on the
fan belts must be checked to ensure that it is correct, and
that the belts have not stretched. It is strongly advised that
this is undertaken by the commissioning engineer, and not
the operator
8.2 Servicing
Warning
Servicing must be carried out on a regular basis, the
maximum interval between services being one year.
It is a requirement that only suitably qualified and competent
persons are allowed to undertake the servicing.
The manufacturers advise that the planned service schedule
as detailed in section 4.1 of the Installation, Commissioning
and Servicing Manual is adopted by the user.
Further details are available from either the commissioning
engineer or from the Manufacturer (details below)
8.3 Start Up Procedure
(a) Enable burner via controller by selecting 'Heat' (Relay 2);
'Heat On'; 'Heat/Auto'.*
(* dependent on control type supplied. Refer to individual
controller operating manual.)
(b) Burner will fire and establish within 60seconds.
(c) As temperature of heater increases, fan will operate.
Registered in England No. 01390934.
Nortek Global HVAC is a registered trademark of Nortek Global HVAC Limited. Because of continuous product innovation, Nortek Global HVAC reserves the right to change
product specification without due notice.
Registered office: The Colmore Building, Colmore Circus Queensway, Birmingham B4 6AT
8.4 Stop procedure
(a) Disable burner by selecting 'Heat OFF'; 'Standby'.*
(* dependent on control type supplied. Refer to individual
controller operating manual.)
(b) The burner will turn off.
(c) The fan motor will continue to run until heat dissipation
allows the fan and limit stat to shut down the fan.
Caution
Do not use the main electrical isolator to turn off the heater,
to do so can cause damage to the heat exchanger and
combustion chamber and thereby invalidate the warranty.
8.5 Shut down procedure
(a) Follow steps 8.4 (a), (b) and (c), when main fan stops turn
main electrical isolator off, and shut gas cocks

8.6 Ventilation only

(a) Enable fan on via controller by selecting 'Fan only'; 'Vent
only'; 'Vent/Manual'.* (*dependent on control type supplied.
Refer to individual controller operating manual.)
(b) Fan will operate without the burner for the set period of
the controller.

8.7 Lockout situations

If either the burner or the fan and limit stat go to lockout,
the lockout must be cleared manually before the ignition
sequence can be re-initiated.
Caution
Repeated or frequent lockouts must be investigated and
their cause determined by a qualified and competent
engineer.
NORTEK GLOBAL HVAC (UK) LTD
Fens Pool Avenue
Brierley Hill
West Midlands DY5 1QA
United Kingdom
Tel: 01384 489 250
Fax: 01384 489 707
bensonsales@nortek.com
www.bensonheating.co.uk

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

6040120135180205 ... Show all

Table of Contents