Honeywell EC7830A Installation Instructions Manual page 8

7800 series
Hide thumbs Also See for EC7830A:
Table of Contents

Advertisement

EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
Terminal No.
Abbreviation
G
Earth G
N
3
AL
4
FAN
5
L1
6
RT
7
LD2
8
PV1
9
M V
10
IGN
F(11)
16
17
ES2
20
LOS
21
PV2
22
SHTR
a
See Table 2.
b
Honeywell has tested this output at 9.8A at PF = 0.5, 58.8A inrush for 100,000 cycles (EN298 approval does not require this
test).
c
2000 VA maximum connected load to relay module.
d
Total load current excluding Burner/Boiler Motor and Firing Rate Outputs cannot exceed 5A, 25A inrush.
Terminal No.
Abbreviation
G
Earth G
N
3
AL
4
FAN
5
L1
6
RT
7
LD2
8
PV1
9
M V
10
IGN
F(11)
16
17
ES2
20
LOS
21
PV2
22
SHTR
a
See Table 2.
b
2000 VA maximum connected load to relay module.
c
Total load current excluding Burner/Boiler Motor and Firing Rate Outputs cannot exceed 5A, 25A inrush for 250,000 cycles.
d
220/240 Vac to 120 Vac, 10 VA stepdown transformer (not provided) must be used to drive the shutter.
66-1092—2
Table 3A. RM7830A Terminal Ratings.
Description
a
Flame Sensor Ground
a
Earth Ground
Line Voltage Common
(Neutral)
Alarm (Normally Open)
Burner/Blower Motor
Line Voltage Supply (L1)
Limits and Burner Control
Airflow Switch Input
Pilot Valve 1 (Interrupted)
Main Fuel Valve
Ignition
Flame Signal
Control Voltage
Preignition Interlock Input
Lockout Input
Pilot Valve 2 (Intermittent)
Shutter
Table 3B. EC7830A Terminal Ratings.
Description
a
Flame Sensor Ground
a
Earth Ground
Line Voltage Common(Neutral)
Alarm(Normally Open)
Burner/Blower Motor
Line Voltage Supply (L1)
Limits and Burner Control
Airflow Switch Input
Pilot Valve 1 (Interrupted)
Main Fuel Valve
Ignition
Flame Signal
Control Voltage
Preignition Interlock Input
Lockout Input
Pilot Valve 2 (Intermittent)
Shutter
8
Ratings
120 Vac, 1A pilot duty, 10A inrush for 5000 cycles.
120 Vac, 4A at PF = 0.5, 20A inrush.
120 Vac (+10/-15%), 50/60 Hz ( ±10%).
120 Vac, 1 mA.
120 Vac, 5A.
120 Vac, 4A at PF = 0.5, 20A inrush.
120 Vac, 4A at PF = 0.5, 20A inrush.
d
120 Vac, 2A at PF = 0.2.
60 to 220 Vac, current limited.
120 Vac (+10/-15%)
120 Vac, 1A, 10A inrush for 5000 cycles.
Carry 5A for 250,000 cycles.
120 Vac, 1 mA.
120 Vac, 4A at PF = 0.5, 20A inrush.
Shutter drive for dynamic self-check flame sensor.
Ratings
220/230/240 Vac, 1A, 10 A inrush for 5000 cycles.
220/230/240 Vac, 4A at PF = 0.5, 20A inrush.
220 to 240 Vac (+10/-15%), 50/60 Hz (±10%).
220/230/240 Vac, 1 mA maximum.
220/230/240 Vac, 5A.
220/230/240 Vac, 4A at PF = 0.5, 20A inrush.
220/230/240 Vac, 4A at PF = 0.5, 20A inrush.
220/230/240 Vac, 2A ignition.
60 to 220 Vac, current limited.
220/230/240 Vac, 1A, 10A inrush for 5000 cycles;
carry 5A for 250,000 cycles.
220/230/240 Vac, 1 mA.
220/230/240 Vac, 1 mA.
220/230/240 Vac, 4A at PF = 0.5, 20A inrush.
Shutter drive for dynamic self-check flame sensor.
b
c
d
d
d
b
c
c
c
c
d