Vacon 8000 solar User Manual page 40

3-phase photovoltaic inverters
Table of Contents

Advertisement

vacon • 39
Shield
21
22 23
OPTD2 /
OPTD6
Connections between drives with OPTD2
Special connection:
In this connection example, the leftmost device is the Master and the others are slaves. The Master
can send and receive data from the slaves. The slaves cannot communicate with each other. Changing
of masters is not possible, the first device is always the Master.
The OPTD2 board in the Master has the default jumper selections, i.e. X6:1-2, X5:1-2. The jumper
positions have to be changed for the slaves: X6: 1-2, X5:2-3.
Max.
number of devices
in line
3
6
12
24
5
Figure 28.Alternative connection of "CAN GND" signal
C
A
N
I H
C
A
N
L
O
CAN
GND
21
OPTD2 /
OPTD6
Max.
speed achieved
[Mbit/s]
12
6
3
1.5
C
A
N
I H
C
A
N
L
O
CAN
GND
22 23
Conn ect the
data GND
tightly to the
chassis on
one point
in the net
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
ELECTRICAL CONNECTION
21
22 23
OPTD2 /
OPTD6
Grounding clamp