service life.
If the battery and UPS are installed in one room, the maximum design environmental
protection shall be determined by the battery, not UPS. That is to say, if use the valve
control battery, the indoor temperature shall be within 15℃~25℃, not 0℃~40℃ (it is
the regulated working temperature range of main equipment). The temperature is allowed
the deviation in a short time; On the premise that the average temperature should
exceed 25℃.

3.3.3 Temperature pickup of battery

The temperature plate of the battery can be installed in the highest temperature position
of battery cupboard (generally at the top), and it is connected directly to UPS control
system. If use the control panel of the battery switch, connect UPS control system
through the control panel of battery switch. This function can regulate the float charge
voltage of battery to make it inversely proportional to battery cupboard/room temperature.
So the battery can be protected from over charge under high temperature enviroment.

3.3.4 Cable incoming

The incoming of battery is from bottom. When the incoming is from bottom, take off the
bottom shielding piece of the equipment, and then you can see the incoming hole.

3.3.5 Structural map of battery configuration

Note: Please pay high attention to the battery connection ,regarding the Negative
Pole"-" , the Positive Pole"+" and the Neutral"N",.
(1) Standard model with internal battery.

Please refer the below sketch Diagram 17-1