Field Wiring - LG ARUN050LMC0 Installation Manual

Hide thumbs Also See for ARUN050LMC0:
Table of Contents

Advertisement

22
!
WARNING
• Follow ordinance of your governmental organization for
technical standard related to electrical equipment, wiring
regulations and guidance of each electric power company.
• Make sure to use specified cables for connections so that no
external force is imparted to terminal connections. If
connections are not fixed firmly, it may cause heating or fire.
• Make sure to use the appropriate type of overcurrent protection
switch. Note that generated overcurrent may include some
amount of direct current.
!
CAUTION
• Some installation site may require attachment of an earth leakage
breaker. If no earth leakage breaker is installed, it may cause an
electric shock.
• Do not use anything other than breaker and fuse with correct
capacity. Using fuse and wire or copper wire with too large capacity
may cause a malfunction of unit or fire.

Field Wiring

Example Connection of Communication Cable
Comp. Module
Power supply
(3N~ 4-wire)
Comp. Module
(Main Switch)
R S T N
Switch
Fuse
Indoor
Power supply
(1~ 2-wire)
N
L
Power cable
(4-wire Cable)
Power cable
(2-wire Cable)
Pull Box
Pull Box
(Installer option)
(Installer option)
Power cable
Power cable
(2-wire Cable)
(2-wire Cable)
Communication cable
(3-wire Cable)
Frequency
Comp. Module
50Hz
380~415V
[Heat Pump]
Between Indoor unit and Outside unit
Communication Cable Wiring
SODU.B SODU.A
IDU.B
IDU.A
CEN.B
3
4
3
4
Hex.
Module
Indoor Unit
The GND terminal at the main PCB is a '-' terminal for dry contact, it is
not the point to make ground connection.
Hex. Module
Power supply
(1~ 2-wire)
Hex. Module
L
N
Power cable
(2-wire Cable)
Communication cable
(2-wire Cable)
Pull Box
Pull Box
(Installer option)
(Installer option)
www.lgcomfortcooling.co.uk
Power cable
Power cable
(2-wire Cable)
(2-wire Cable)
[Indoor Units]
Voltage range(V)
HEX Module
Indoor Unit
220~240V
220~240V
Compressor
CEN.A
DRY1
DRY2
GND
12V
Module
3
4
3
4
Indoor Unit
Indoor Unit
!
WARNING
• Indoor Unit ground wires are required for preventing electrical shock
accident during current leakage, Communication disorder by noise
effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect
each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an
integrated manner because this system consists of the equipment
utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase,
momentary blackout or the power goes on and off while the
product is operating, attach a reversed phase protection circuit
locally. Running the product in reversed phase may break the
compressor and other parts.
Example) Connection of transmission wire
[BUS type]
- Connection of communication
cable must be installed like
below figure between indoor
unit to outside unit.
Compressor
Heat Exchanger
Module
Module
Example) Connection of power and communication cable
- Case of Rear side pipe draw out.
- Case of Top side pipe draw out.
Power cable,
Communication cable
[STAR type]
- Abnormal operation can be
caused by communication
defect, when connection of
communication cable is installed
like below figure(STAR type).
Compressor
Heat Exchanger
Module
Module
Power cable,
Communication cable

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Arun050gme0

Table of Contents