Heat Exchanger Module Installation

- Select and mark the position for fixing bolts.
- Drill the hole for set anchor on the face of ceiling.
!
CAUTION
• Tighten the nut and bolt to prevent unit falling
- Insert the set anchor and washer onto the suspension bolts for
locking the suspension bolts on the ceiling.
- Mount the suspension bolts to the set anchor firmly.
- Secure the installation plates onto the suspension bolts (adjust level
roughly) using nuts, washers and spring washers.
Old building
1 Set anchor
2 Plate washer
3 Spring washer
4 Nut
5 Suspension
bolts

Method when insatalling the ducting

- Ducting is to be field supplied
- For prevent water from flowing into the Heat exchanger module,
Make sure the ductiong has slopes down
- You Protect the ducting against reverse airflow from wind.
- If the suction ducting or discharge ducting is connected with the
inside air, it might be impossible to reach the desired room
temperature.
- Connect suction ducting and discharge ducting with the outside air.
Method connect the refrigerant piping to the
Heat Exchanger Module.
1. Cut the liquid pipe and gas pipe.
2. Burrs removal
- Completely remove all burrs from the cut cross section of
pipe/tube.
- Put the end of the copper tube/pipe to downward direction as you
remove burrs in order to avoid to let burrs drop in the tubing.
New building
3. Wrap the pipe with a wet cloth.
4. Braze the liquid pipe and gas pipe.
5. Remove the wet cloth.
Insulation, others : Insulate the joint and tubes
completely.
www.lgcomfortcooling.co.uk
Thermal insulation : All thermal insulation must comply with local
requirement.
Heat Exchanger Module
Copper
Slanted
tube
90°
Union for liquid pipe
Hose crip for thermal insulator
(Local supply)
Thermal insulator for refrigerant pipe
(Local supply)
Union for gas pipe
Thermal insulator for refrigerant pipe
(Local supply) Thermal insulator for
piping(Local supply)
Overlap with thermal
insulator for piping.
Hose crip for thermal insulator(Local supply)
Make sure that there is no clearance here.
Uneven Rough
Refrigerant pipe and thermal
insulator(Local supply)