5.2 Connecting AC Output Power Cables

Connect the SUN2000 to the AC power distribution frame (PDF) or power grid over AC input
power cables.
Prerequisites
An independent there-phase circuit breaker for each inverter must be installed at the output
side to ensure that the inverter can be securely disconnected. See
to select the specifications of breaker.
It is not allowed for several inverters to use the same circuit breaker.
It is not allowed to connect loads between inverter and circuit breaker.
Context
Huawei recommends a soft cable for ease of installation. The outer diameter of the conductor
should be less than or equal to 4.2 mm.
Table 5-1 Recommended AC output power cable specifications
Inverter
Cable Type
Model
Range
SUN2000
4-core
-8KTL
outdoor
cable (3+N)
SUN2000
5-core
-10KTL
outdoor
cable
SUN2000
(3+N+PE)
-12KTL
SUN2000
-15KTL
SUN2000
-17KTL
SUN2000
-20KTL
SUN2000
-23KTL
SUN2000
3-core
-24.5KTL
outdoor
Issue 07 (2014-07-30)
Cross-sectional Area
(mm
2
Recommended
Range
Value
4–10
4-core outdoor
(12AWG–
cable (3+N)
8AWG)
6–10
(10AWG–
8AWG)
3-core outdoor
cable
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Table 5-1
lists the specifications.
External Cable Diameter (mm)
)
Recommended
Range
Value
4 (12AWG)
11–20
NOTE
6 (10AWG)
5 Electrical Connections
10 Technical Specifications
Recommended
Value
15
When the outer
cable
diameter
ranges from 11
mm to 13 mm,
add
cable
clamps.
When the outer
cable
diameter
ranges from 16
mm to 20 mm,
strip a seal ring
from the cable
sealing
cover
interior.
When the outer
diameter of an
armored
cable
exceeds 20 mm,
strip the jacket
and
armored
layer and take
waterproof
and
45