Daikin FTXM Series Installation Manual

Daikin FTXM Series Installation Manual

Air conditioner

Advertisement

Quick Links

3P384095-2 M14B149
DAIKIN AIR CONDITIONER
Safety Precautions (1)
Read the precautions in this manual
This appliance is filled with R32.
carefully before operating the unit.
• The precautions described herein are classified as WARNING and CAUTION. They both contain important information
regarding safety. Be sure to observe all precautions without fail.
• Meaning of WARNING and CAUTION notices
WARNING
Failure to follow these instructions properly may result in personal injury or loss of life.
CAUTION
Failure to follow these instructions properly may result in property damage or personal injury, which may be serious depending on the circumstances.
• The safety marks shown in this manual have the following meanings:
Be sure to follow the instructions.
Be sure to establish an earth connection.
Never attempt.
• After completing installation, conduct a trial operation to check for faults and explain to the customer how to operate
the air conditioner and take care of it with the aid of the operation manual.
WARNING
• Ask your dealer or qualified personnel to carry out installation work.
Do not attempt to install the air conditioner yourself. Improper installation may result in water leakage, electric shocks or fire.
• Install the air conditioner in accordance with the instructions in this installation manual.
Improper installation may result in water leakage, electric shocks or fire.
• Be sure to use only the specified accessories and parts for installation work.
Failure to use the specified parts may result in the unit falling, water leakage, electric shocks or fire.
• Install the air conditioner on a foundation strong enough to hold the weight of the unit.
A foundation of insufficient strength may result in the equipment falling and causing injury.
• Electrical work must be performed in accordance with relevant local and national regulations and with the instructions in this installation manual.
Be sure to use a dedicated power supply circuit only.
Insufficient power supply and improper workmanship may result in electric shocks or fire.
• Use a cable of suitable length.
Do not use tapped wires or an extension lead, as this may cause overheating, electric shocks or fire.
• Make sure that all wiring is secured, the specified wires are used, and that there is no strain on the terminal
connections or wires.
Improper connections or securing of wires may result in abnormal heat build-up or fire.
• When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the wires so that the
control box lid can be securely fastened.
Improper positioning of the control box lid may result in electric shocks, fire or overheating terminals.
• If refrigerant gas leaks during installation, ventilate the area immediately.
Toxic gas may be produced if the refrigerant comes into contact with fire.
• After completing installation, check for refrigerant gas leakage.
Toxic gas may be produced if the refrigerant gas
leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker.
• When installing or relocating the air conditioner, do not let any other substances besides R32, such as air, enter the refrigerant circuit.
The presence of air or other foreign matter in the refrigerant circuit causes an abnormal pressure rise, which may result in equipment damage and even injury.
• During installation, attach the refrigerant piping securely before operating the compressor.
If the refrigerant pipes are not attached and the stop valve is
open when the compressor is operated, air will be sucked in, causing abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury.
• During pump down, stop the compressor before removing the refrigerant piping.
If the compressor is still operating and the stop valve is open during pump down,
air will be sucked in when the refrigerant piping is removed, causing abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury.
• Be sure to earth the air conditioner.
Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead. Imperfect earthing may result in electric shocks.
• Be sure to install an earth leakage circuit breaker.
Failure to install an earth leakage circuit breaker may result in electric shocks or fire.
• Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
• The appliance must be stored in a room without continuously operating ignition sources (for example: open flames,
an operating gas appliance or an operating electric heater).
• Do not pierce or burn.
• Be aware that refrigerants may not contain an odour.
• The appliance must be installed, operated and stored in a room with a floor area larger than 3.9m
.
2
• Comply with national gas regulations.
Indoor Unit Installation Drawings
How to attach the indoor unit.
Hook the tabs of the bottom frame
to the
A
mounting plate.
If the tabs are difficult to hook,
remove the front grille.
How to remove the indoor unit.
Push up the marked area (at the
A Mounting plate
The mounting plate
lower part of the front grille) to
should be installed on a
release the tabs. If it is difficult to
wall which can support the
release, remove the front grille.
Front grille
weight of the indoor unit.
Service lid
The service lid is
removable.
Opening method
1) Remove the service
lid screws.
2) Pull out the service
B
Mounting plate fixing
lid diagonally down
screws M4 × 25L (9 pcs)
in the direction of
the arrow.
3) Pull down.
30mm or more
from ceiling
INTELLIGENT EYE
Front panel
sensor
Caulk pipe
hole gap
with putty.
The flare connection should
be installed outdoors.
Cut thermal insulation
50mm or more
pipe to an appropriate
from walls
length and wrap it with
(on both sides)
tape, making sure that no
M4 × 16L
Unit dimensions
gap is left in the insulation
M4 × 16L
pipe's cut line.
M4 × 16L
Height
340mm
Width
1200mm
M
Screw cover (3 pcs)
Depth
240mm
Front grille fixture
Wrap the thermal insulation
pipe with the finishing tape
How to remove front grille fixture
from bottom to top.
1) Insert the tool into the groove of the front grille fixture.
Air filters
Front grille fixture
Bottom of indoor unit
2) Turn the tool 90° in the direction of the arrow.
C Titanium apatite photocatalytic
D Wireless
air-purifying filter (3 pcs)
remote controller
Titanium apatite photocatalytic
3) Take out the front grille fixture.
air-purifying filter
F
Fixing screws for
remote controller
holder M3 × 20L
Filter frame
(2 pcs)
Tab
Air filter
INTELLIGENT EYE sensor
CAUTION
• Do not hit or forcefully push the intelligent-eye sensor. This can lead to damage and malfunction.
• Do not place large objects near the sensor. Also keep heating units or humidifiers outside the sensor's detection area.
Safety Precautions (2)
CAUTION
• Do not install the air conditioner at any place where there is a danger of flammable gas leakage.
In the event of a gas leakage, build-up of gas near the air conditioner may cause a fire to break out.
The two-dimensional bar code
• While following the instructions in this installation manual, install drain piping to ensure proper drainage and insulate
is a manufacturing code.
the piping to prevent condensation.
Improper drain piping may result in indoor water leakage and property damage.
• Tighten the flare nut as specified, such as with a torque wrench.
If the flare nut is too tight, it may crack after prolonged use, causing refrigerant leakage.
• Only qualified personnel can handle, fill, purge and dispose of the refrigerant.
 This product is not designed for re-packing. In case of re-packing contact to Daikin dealer.
Accessories
Mounting plate fixing
A
Mounting plate
1
B
screws M4 × 25L
D
Wireless remote controller
1
E
Remote controller holder
Dry batteries AAA. LR03
Indoor unit fixing screws
G
2
H
(alkaline)
M4 × 12L
K
Operation manual
1
L
Installation manual
Choosing an Installation Site
• Before choosing the installation site, obtain user approval.
7) the unit is away from electronic ignition type
1.
fluorescent lamps (inverter or rapid start type) as
Indoor unit
they may affect the remote controller range,
• The indoor unit should be positioned in a place where:
8) the unit is at least 1m away from any television or radio set
1) the restrictions on the installation requirements specified
(the unit may cause interference with the picture or sound),
in the indoor unit installation drawings are met,
9) the unit can be installed at the recommended height (2.5m),
2) both the air inlet and air outlet are unobstructed,
10) no laundry equipment is located.
3) the unit is not exposed to direct sunlight,
2.
4) the unit is away from sources of heat or steam,
Wireless remote controller
5) there is no source of machine oil vapour (this may
• Turn on all the fluorescent lamps in the room, if any,
shorten the indoor unit service life),
and find a location where the remote controller signals
6) cool (warm) air is circulated throughout the room,
are properly received by the indoor unit (within 7m).
Installation Tips (1)
1.
Removing and installing the front panel
Removal method
Hook fingers on the tabs on the left and right of the main body, and open until the
panel stops. Slide the front panel sideways to disengage the front panel shaft.
Then pull the front panel toward you to remove it.
Installation method
Align the tabs of the front panel with the grooves, and push all the way in. Then close slowly.
Push the centre of the lower panel surface firmly to engage the tabs.
2.
Removing and installing the front grille
Removal method
1) Remove the front panel to remove the air filter.
2) Remove 6 screws from the front grille.
3) In front of the
mark on the front grille, there are 4 upper hooks.
Lightly pull the front grille toward you with one hand, and push down on the hooks with the fingers of your other hand.
<When there is insufficient work space because the unit is close to ceiling>
Place both hands under the centre of the front grille, and while pushing up,
pull it toward you.
Installation method
1) Install the front grille and firmly engage the upper hooks (4 locations).
2) Install 6 screws of the front grille.
2) Pull toward you.
3) Install the air filter and then mount the front panel.
Indoor Unit Installation (1)
1.
Installing the mounting plate
• The mounting plate should be installed on a wall which can support the weight of the indoor unit.
A Mounting
plate
1) Temporarily secure the mounting plate to the wall, make sure that the panel is completely level, and
Tab
mark the boring points on the wall.
2) Secure the mounting plate to the wall with screws.
Bottom frame
Recommended mounting plate retention spots and dimensions
Mark (rear side)
Recommended mounting plate
The removed pipe port
retention spots (9 spots in all)
cover can be kept in the
131
(Bolt size: M10)
(Bolt size: M10)
mounting plate pocket.
Removed pipe
port cover
φ80
65.3
161
47
554
A Mounting
1200
plate
Drain hose
Through-the-wall
Place the pipe port cover
position
hole φ80mm
in this pocket.
2.
Drilling a wall hole and installing wall embedded pipe
• For metal frame or metal board walls, be sure to use a wall embedded
pipe and wall hole cover in the feed-through hole to prevent possible heat,
electrical shock, or fire.
• Be sure to caulk the gaps around the pipes with caulking material to
prevent water leakage.
1) Drill a feed-through hole with a 80mm diameter through the wall at a
downward angle toward the outside.
2) Insert a wall embedded pipe into the hole.
3) Insert a wall hole cover into wall pipe.
4) After completing refrigerant piping, wiring, and drain piping, caulk the pipe hole gap with putty.
3.
Installing the indoor unit
3-1. Right-side, right-back, or right-bottom piping
1) Attach the drain hose to the underside of the refrigerant pipes
with an adhesive vinyl tape.
Before screwing
2) Wrap the refrigerant pipes and drain hose together with
the remote
J
insulation tape.
controller holder
to the wall, make
sure that control
signals are
3) Pass the drain hose and refrigerant pipes through the wall hole,
properly received
then set the indoor unit on the mounting plate hooks by using the
by indoor unit.
markings at the top of the indoor unit as a guide.
4) Open the front panel, then open the service lid.
E
(Refer to Installation Tips.)
Remote
controller holder
5) Pass the inter-unit wire from the outdoor unit through the feed-
through wall hole and then through the back of the indoor unit.
Pull them through the front side.
Bend the ends of cable tie wires upward for easier work in advance.
(If the inter-unit wire ends are to be stripped first, bundle the wire
lead ends with adhesive tape.)
6) Press the bottom frame of the indoor unit with both hands to set it
on the mounting plate hooks. Make sure that the wire leads do
not catch on the edge of the indoor unit.
Indoor Unit Installation (2)
3-2. Left-side, left-back, or left-bottom piping
1) Attach the drain hose to the underside of the refrigerant
pipes with adhesive vinyl tape.
2) Be sure to connect the drain hose to the drain port in
place of the drain plug.
How to set the drain hose.
Insert drain hose and tighten fixing screw.
Forgetting to attach this may cause water leakages.
N004
The drain hose is on the back of the unit.
Drain hose attachment position
Attachment on the left side
Fixing screw
Titanium apatite photocatalytic
Drain hose
9
C
3
air-purifying filters
Fixing screws for remote
3) Shape the refrigerant pipes along the pipe path
1
F
2
controller holder M3 × 20L
marking on the mounting plate.
3
J
Insulation tape
1
4) Pass the drain hose and refrigerant pipes through
the wall hole, then position the indoor unit on the
1
M
Screw cover
3
mounting plate hooks, using the
the top of the indoor unit as a guide.
5) Pull in the inter-unit wire.
6) Connect the refrigerant pipes.
7) In case of pulling the drain hose through the back of the indoor
unit, wrap the refrigerant pipes and drain hose together with
J insulation tape as shown in the right figure.
8) While exercising care so that the inter-unit wiring does not catch the
indoor unit, press the bottom edge of the indoor unit with both hands until
it is firmly caught by the mounting plate hooks. Secure the indoor unit to
the mounting plate with the H indoor unit fixing screws (M4 × 12L).
3-3. Wall embedded piping
Follow the instructions given under left-side, left-back, or
left-bottom piping.
1) Insert the drain hose to this depth so it won't be pulled out of
the drain pipe.
4.
Wiring
1) Strip wire ends (20mm).
2) Match wire colours with terminal numbers on the indoor and
outdoor unit's terminal blocks and firmly secure the wires in
the corresponding terminals with the screws.
3) Connect the earth wires to the corresponding terminals.
4) Pull the wires lightly to make sure they are securely
connected, then secure them with the wire retainer.
Push the front panel
5) In case of connecting to an adapter system, run the remote
shaft of the front panel
into the groove.
controller cable and attach the S21.
(Refer to "5. When connecting to an HA system".)
Upper hook
6) Shape the wires so that the service lid fits securely, then close the
 mark area
Push
Upper hook
down.
(4 locations)
service lid.
WARNING
1) Push up.
Do not use tapped wires, extension cords, or starburst connections, as they may cause overheating, electrical
CAUTION
shock,or fire.
Be sure to wear protection
Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump,
gloves.
etc., from the terminal block.) Doing so may cause electric shock or fire.
Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.
Refrigerant Piping Work (2)
2.
Refrigerant piping
CAUTION
• Use the flare nut fixed to the main unit.
(This is to prevent cracking of the flare nut as a result of deterioration over time.)
• To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare.
(Use refrigeration oil for R32.)
• Use a torque wrench when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.
Place a leveler on these tabs.
134
(Bolt size: M10)
• Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully
with the torque wrenches.
• Refrigerant oil for R410A can also be used for application to the inner flare.
Use a tape
measure
as shown.
Flare nut
Position
φ80
the end of
the tape
Do not apply refrigeration
measure
oil to the flare nut to avoid tightening
Gas pipe end
at
.
182.5
89
with excessive torque.
Liquid pipe end
unit: mm
61.8-75.4N
(630-770kgf
Inside
Outside
Wall embedded pipe
(field supply)
2-1. Caution on piping handling
Caulking(field supply)
1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe
Wall hole cover
bender for bending.
(field supply)
2-2. Selection of copper and heat insulation materials
• When using commercial copper pipes and fittings, observe the following:
1) Insulation material: Polyethylene foam
Heat transfer rate: 0.041 to 0.052W/mK (0.035 to 0.045kcal/mh°C)
Refrigerant gas pipe's surface temperature reaches 110°C max.
Right-side piping
Right-back piping
Choose heat insulation materials that will withstand this temperature.
Remove pipe port cover
here for right-side piping.
Right-bottom
2) Be sure to insulate both the gas and liquid piping and observe the
piping
Bind refrigerant
pipe and drain
Remove pipe port cover
insulation dimensions as below.
hose together with
here for right-bottom piping.
J
insulation tape.
Piping size
Minimum bend radius
A
Mounting plate
Gas side
O.D. 15.9mm
Liquid side
O.D. 6.4mm
3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
Hang indoor unit's hook here.
When stripping the
A
Mounting
ends of inter-unit
plate
wire in advance,
bundle the wire
Inter-unit
lead ends with tape.
wiring
Wire guide
5.
When connecting to an HA system
Remove pipe port
cover here for
1) Remove the front grille.
left-side piping.
Left-side
(6 screws, 3 front grille
piping
fixtures)
Remove pipe port cover here for left-bottom piping.
Left-back
piping
Left-bottom piping
2) Remove the electrical
wiring box. (1 screw)
How to set the drain plug.
3) Remove the metal plate
Do not apply
electrical wiring box cover.
lubricating oil
(refrigerant oil) to
(4 tabs)(See Fig.1)
the drain plug when
inserting it.
4) Attach the connection
Attachment on the right side (factory default)
The application of
lubrication oil to the
cord to the S21 connector
drain plug will
Fixing screw
and pull the harness out
deteriorate the plug
Insert a hexagon
to cause drain
through the notched part in the figure. (See Fig.2)
wrench (4mm)
leakage from the
Drain hose
plug.
Front side of unit
5) Replace the electrical wiring box cover as it was, and pull the harness around, as shown in the figure.(See Fig.3)
6.
Drain piping
1) Connect the drain hose, as described below.
Drain
hose
A
Mounting plate
markings at
Caulk this hole
with putty or
Wrap
J
insulation tape
Bind with vinyl
around the bent portion of the
caulking material.
tape.
refrigerant pipe.
Overlap at least half the width
of the
J
insulation tape with
each turn.
Inter-unit wire
A
Mounting
2) Remove the air filters and pour some water
Drain hose
plate
Refrigerant
into the drain pan to check the water flows
pipes
smoothly.
Bottom frame
M4 × 12L (3 locations)
H
Inner wall
Insert drain hose to this
depth so it won't be
pulled out of drain pipe.
50mm
Drain hose
or more
Vinyl chloride
drain pipe
Outer wall
(VP-30)
Terminal block
Electrical wiring box
Shape wires so
1.
that the service
Flaring the pipe end
lid will fit securely.
1) Cut the pipe end with a pipe cutter.
Firmly secure the wire
2) Remove burrs with the cut surface facing
retainer so that wires
Use the
sustain no external stress.
specified
downward so that the chips do not enter the
wire type.
Wire retainer
pipe.
Firmly fix the wires with
Outdoor unit
the terminal screws.
3) Put the flare nut on the pipe.
Inter-unit wire
4-core 1.5mm² or more
1 2 3
L N
4) Flare the pipe.
60245 IEC 57
5) Check that the flaring is properly made.
1
Indoor
2
unit
3
Firmly fix the wires with
WARNING
the terminal screws.
• Do not use mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
• Never install a drier to this R32 unit in order to guarantee it's lifetime.
• The drying material may dissolve and damage the system.
• Incomplete flaring may cause refrigerant gas leakage.
1.
Trial operation and testing
• Trial operation should be carried out in either COOL or HEAT operation.
1-1 Measure the supply voltage and make sure that it is within the specified range.
1-2 In COOL operation, select the lowest programmable temperature; in HEAT operation,
select the highest programmable temperature.
1-3 Carry out the trial operation in accordance with the operation manual to ensure that all
functions and parts, such as louvres movement, are working properly.
• For protection, the system disables restart operation for 3 minutes after it is turned off.
• When trial operation is conducted in the HEAT operation directly after the circuit breaker is turned on, in
1-4 After trial operation is complete, set the temperature to a normal level (26°C to 28°C in COOL
operation, 20°C to 24°C in HEAT operation).
Apply oil
Tighten
Torque wrench
• When operating the air conditioner in COOL operation in winter, or HEAT operation in summer, set it to the trial
Apply refrigeration oil to the
inner surface of the flare.
operation mode using the following method.
Spanner
Flare nut
Do not apply refrigeration
oil to the outer surface.
Piping union
Flare nut tightening torque
Gas side
Liquid side
15.9mm
6.4mm
m
14.2-17.2N
m
cm)
(144-175kgf
cm)
• The air conditioner draws a small amount of power in its standby mode. If the system is not to be used for some
time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.
• If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original operation
Wall
Be sure to
mode when the circuit breaker is opened again.
place a cap.
2.
Rain
If no flare cap is
Test items
available, cover
the flare mouth
with tape to keep
dirt or water out.
Indoor and outdoor units are installed properly on
solid bases.
No refrigerant gas leaks.
Inter-unit wire
Gas pipe
Liquid pipe
Refrigerant gas and liquid pipes and indoor drain
hose extension are thermally insulated.
Draining line is properly installed.
Gas pipe
Liquid pipe
System is properly earthed.
insulation
insulation
Finishing tape Drain hose
The specified wires are used for inter-unit wiring
connections.
Thermal insulation size Thermal insulation
Piping thickness
thickness
Indoor or outdoor unit's air inlet or air outlet are
50mm or more
1.0mm (C1220T-O)
I.D. 16-20mm
unobstructed.
10mm Min.
30mm or more
0.8mm (C1220T-O)
I.D. 8-10mm
Stop valves are opened.
Indoor unit properly receives remote controller
commands.
will appear when the MODE button is pressed.*
* Check that the jumper (J8) has not been cut. If it has been
cut, contact the service shop.
Indoor Unit Installation (3)
HA connector
(S21)
Tab
Pull
Pull
Slide
Tab
Lay the HA cord as
shown in the figure.
Slide
HA connector
Screw
(S21)
Metal plate
electrical cover
Main body
Fig.1
Fig.2
Fig.3
3) When drain hose requires extension, obtain an
extension hose with an inner diameter of 16mm.
The drain hose should
Be sure to thermally insulate the indoor
be inclined downward.
section of the extension hose.
No trap is permitted.
Extension drain hose
Indoor unit
drain hose
Do not put the end
of the hose in water.
Heat insulation tube
(field supply)
4) When connecting a rigid polyvinyl chloride pipe
(nominal diameter 13mm) directly to the drain
hose attached to the indoor unit as with embedded
piping work, use any commercially available drain
socket (nominal diameter 13mm) as a joint.
Drain hose supplied with
Commercially available drain
Commercially available rigid
the indoor unit
socket
polyvinyl chloride pipe
(nominal diameter 13mm)
(nominal diameter 13mm)
Refrigerant Piping Work (1)
(Cut exactly at
right angles.)
Remove burrs
Flaring
Set exactly at the position shown below.
A
Flare tool for R32 or R410A
Conventional flare tool
Clutch-type
Clutch-type (Rigid-type)
Wing-nut type (Imperial-type)
Die
A
0-0.5mm
1.0-1.5mm
1.5-2.0mm
Check
The pipe end must
Flare's inner
be evenly flared in
surface must
be flaw-free.
a perfect circle.
Make sure that the
flare nut is fitted.
Trial Operation and Testing
some cases no air will be output for about 10 minutes in order to protect the air conditioner.
1) Press
and select the trial operation (COOL or HEAT).
2) Press
to turn on the system.
3) Press both of
and
at the same time.
4) Press
, select "
",and press
for confirmation.
• Trial operation will stop automatically after about 30 minutes.
To stop the operation, press
.
• Some of the functions cannot be used in the trial operation mode.
Test items
Symptom
Check
Fall, vibration, noise
Incomplete cooling/heating function
Water leakage
Water leakage
Electrical leakage
No operation or burn damage
Incomplete cooling/heating function
Incomplete cooling/heating function
No operation
No heating
Jumper (J8)

Advertisement

loading
Need help?

Need help?

Do you have a question about the FTXM Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Daikin FTXM Series

  • Page 1 Metal plate N004 lubricating oil electrical cover  This product is not designed for re-packing. In case of re-packing contact to Daikin dealer. The drain hose is on the back of the unit. (refrigerant oil) to (4 tabs)(See Fig.1) the drain plug when Read the precautions in this manual This appliance is filled with R32.
  • Page 2 (2) ‫ﺗﻨﺒﻴﻬﺎﺕ ﺍﺣﺘﻴﺎﻃﻴﺔ ﺣﻮﻝ ﺍﻟﺴﻼﻣﺔ‬ (3) ‫ﺗﺮﻛﻴﺐ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬ (2) ‫ﺗﺮﻛﻴﺐ ﺍﻟﻮﺣﺪﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬ 3P384095-2 M14B149 ‫ﻣﻜﻴﻒ ﺍﻟﻬﻮﺍﺀ ﻣﻦ ﺩﺍﻳﻜﻦ‬ ‫ﺩﻟﻴﻞ ﺍﻟﺘﺮﻛﻴﺐ‬ ‫ﺗﻨﺒﻴﻪ‬ HA ‫ﻋﻨﺪ ﺗﻮﺻﻴﻠﻪ ﺑﻨﻈﺎﻡ‬ ‫3-2 . ﲤﺪﻳﺪ ﺍﻷﻧﺒﻮﺏ ﺍﳉﺎﻧﺒﻲ ﺍﻷﻳﺴﺮ ﺃﻭ ﺍﳋﻠﻔﻲ ﺍﻷﻳﺴﺮ ﺃﻭ ﺍﻟﺴﻔﻠﻲ ﺍﻷﻳﺴﺮ‬ ‫ﺍﻧﺰﻉ ﻏﻄﺎﺀ ﻣﻨﻔﺬ‬ (S21) HA ‫ﺍﳌﻮﺻﻞ‬...