P7640A,B DIFFERENTIAL PRESSURE SENSORS
APPENDIX
IMPORTANT
This page is only for models with date code prior to 0816.
Pre 0816 Date Code Configuration
Select the proper output, mode, and pressure range using the switches and jumpers:
1. Select output using the output switch:
a. Current: mA (then skip to step 3), or
b. Voltage: Volt.
2. Select 0-10 Vdc or 0-5 Vdc using jumper J4.
3. Select bi- or uni-directional mode using jumper J5.
NOTE: Setting for 0 to 1 in. w.c. and bi-directional will give output from -1.0 to 1.0 in. w.c.
4. Select appropriate full-scale pressure range using the slide switch.
NOTE: Note that either the 1 in. w.c. or 10 in. w.c. scale is marked. This is the available scale for that given
model. When the range is changed, the LCD models momentarily indicate selected range.
WIRING (FIG. 4 THROUGH 5)
CAUTION
Equipment Damage Hazard. Can damage the device beyond repair.
Disconnect power supply before installation.
NOTE: Wiring to the ZERO terminals is optional.
ZERO
PWR OUT COM ZERO
CONTROLLER,
METER OR
RECORDER
+
INPUT SIGNAL
COMMON
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
POLARIZED SECONDARY INDICATIONS FOR USE WITH DC POWER
SUPPLY ONLY.
DRY CONTACT TO AUTOMATICALLY ZERO THE SENSOR UPON
3
CLOSURE. (OPTIONAL)
Fig. 4. Wiring for voltage (Vdc) output.
LonSpec™ is a trademark of Echelon® Corporation.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
RANGE
10" 1"
1.0
10
5
.5
2.5
.25
1.0
.1
MODE
BI/UNI
VOLT
mA
VOLT
5V/10V
3
+
L1
1
2
L2
+
By using this Honeywell literature, you agree that Honeywell will have no liability for any
damages arising out of your use or modification to, the literature. You will defend and indemnify
Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages,
including attorneys' fees, arising out of, or resulting from, any modification to the literature by you.
® U.S. Registered Trademark
© 2014 Honeywell International Inc.
62-0210—07
M.S. Rev. 07-14
Printed in United States
ZERO
PWR OUT COM ZERO
CONTROLLER,
METER OR
RECORDER
+
INPUT SIGNAL
COMMON
1
DRY CONTACT TO AUTOMATICALLY ZERO THE SENSOR
UPON CLOSURE. (OPTIONAL)
Fig. 5. Wiring for current (mA) output.
RANGE
10" 1"
10
1.0
5
.5
2.5
.25
1.0
.1
MODE
BI/UNI
VOLT
mA
VOLT
5V/10V
1
12 TO 40 Vdc
POWER SUPPLY
+
M22555A