DC Testing AWA Unit
9)
If and when the charging current drops below 8-9uA, move the Function knob to the
11uA/div position.
10) At the end of the test, the AWA will automatically shutdown the PP24. A Discharge Bar
will appear on the AWA screen. Wait until the Discharge Bar disappears before moving
or touching the test leads.
11) Close the DC Tests screen and save the data by selecting the yellow Save Data button
on the AWA.
12/7/2009 | 71-026 V2