Summary of Contents for Froling Lambdatronic S 3200
Page 1
Version 50.04 - Build 05.09 Translation of the original German operating instructions for technicians and operators Read and follow the instructions and safety information! Technical changes, typographical errors and omissions reserved! B0361214_en | Edition 21/07/2014 Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Controller check 4.1.2 Check on the connected units 4.1.3 System Check Initial startup 4.2.1 Changing the operating level 4.2.2 Setting the system type 4.2.3 Before heating up for the first time Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Page 3
5.9.1 Status displays for the diff. control 5.9.2 Temperature settings for the diff. control 5.9.3 Service parameters for the diff. control 5.10 Menu - Circulation pump 5.10.1 Status display for the circulation pump Operating Instructions Lambdatronic S 3200 | B0361214_en...
Page 4
Changing the date 5.12.10 Changing the time 5.12.11 Standard settings 5.12.12 Current user level 5.12.13 System type 5.13 PWM / 0 - 10V settings Troubleshooting Procedure for fault messages Setting protocol Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Please read and follow the operating instructions, in particular the safety information contained therein. Keep them available next to the boiler. These operating instructions contain important information about operation, electrical connection and troubleshooting for the Lambdatronic S 3200 control. NOTICE The values given in the parameter lists are examples, and should not be used as standard values! The constant further development of our products means that there may be minor dif‐...
Boiler sensor BS (25) PDM / 0-10V Pump 1 (26) Induced draught (27) Connection cable 3 x 1.5 mm , power supply Connection cable 3 x 0.75 mm , analysis of current speed Operating Instructions Lambdatronic S 3200 | B0361214_en...
❒ The power supply line (mains connection) must be fitted with a 16A fuse by the customer. If a safety overload switch is used it should be a type with 16A. 2.1.3 Connecting the flue gas sensor green-yellow Core module red + blue - Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Core module Connecting a HCP 0 up to max. 5 Ampere: Connection as burner relays: To oil boiler control: floating contact for burner Core module release 2.1.5 Valve for flue gas condenser connection Operating Instructions Lambdatronic S 3200 | B0361214_en...
Setback mode Ignores the heating phases Override circuit Ignores the setback Handwheel… Allows you to adjust the temperature by +/- 3°C IMPORTANT! See assembly instructions/functional description for room temperature sensor FRA Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
➥ Make sure that the cables are configured correctly (polarity) in accordance with the connection diagram of the pump! Important! When using a Froling pump assembly: ⇨ See "Connection diagrams according to pump types" [page 20] Operating Instructions Lambdatronic S 3200 | B0361214_en...
3 x 1.5mm , fuse 10A Pump 1/2 (10/11) Connection cable 3 x 1.5mm , max. 1.5A / 230V / 280W 1. YMM as per ÖVE-K41-5 or H05VV-F as per DIN VDE 0881-5 Operating Instructions Lambdatronic S 3200 | B0361214_en...
Connection example: The outer cable L(bn) should be connected to the outer cable of the respective mains supply of the module or to the core module, HCP0/burner relay output at pin “LV”. Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
➥ Make sure that the cables are configured correctly (polarity) in accordance with the connection diagram of the pump! IMPORTANT! When using a Froling pump assembly: ⇨ See "Connection diagrams according to pump types" [page 20] Operating Instructions Lambdatronic S 3200 | B0361214_en...
Connection cable 3 x 1.5mm Return mixer (3) Connection cable 4 x 0.75mm , max. 0.15A / 230V 1. YMM as per ÖVE-K41-5 or H05VV-F as per DIN VDE 0881-5 Connection example Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Page 17
Connect return mixer module and hydraulic module with bus cable Use delivered mains cable for connection to terminal block. Return sensor Core module (FRKEM 22) Hydraulic module (FRHYU 14) Mains Plug Main switch Operating Instructions Lambdatronic S 3200 | B0361214_en...
LIYCY paired 2x2x0.5 should be used. The connection to the 5-pin plugs should be carried out according to the following diagram: Braided shield Braided shield White White CAN L CAN L Green Green CAN H CAN H Yellow Yellow Brown Brown Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
If the contacts at the base of the end jumper are not bridged (image left), it is referred to as “not set". In this case there is no bus termination. If the contacts are closed (im‐ age right), the end jumper is set and the bus connection is terminated. Operating Instructions Lambdatronic S 3200 | B0361214_en...
Page 21
- brown wire to earth - white wire to plus Do not use the other two wires (blue, black) and insu‐ late if necessary Operating Instructions Lambdatronic S 3200 | B0361214_en...
The status LED shows the operating status of the system: ▪ GREEN flashing (interval: 5 sec OFF, 1 sec ON): Off ▪ GREEN constant: BOILER SWITCHED ON ▪ ORANGE flashing: WARNING ▪ RED flashing: FAULT Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Shown when the DHW tank or return temperature control pump is active. Shown when the heating circuit or storage tank loading pump is ac‐ tive. Shows the status of the heating circuit mixer. Operating Instructions Lambdatronic S 3200 | B0361214_en...
Overview of the basic functions Function keys 3.2 Function keys The function keys of the Lambdatronic S 3200 have dual functions. Different functions can be performed with long or short keystrokes, using the following definitions of key‐ stroke duration: Short keystroke …….. < 1 second Long keystroke ……..
The mode is indicated by the tap symbol on the sta‐ BOILER ON tus line. Domestic hot water loading is controlled Summer mode started according to the program that is set, the heating cir‐ cuit controller is deactivated. Operating Instructions Lambdatronic S 3200 | B0361214_en...
The room temperature is reduced to the preset set‐ back temperature until automatic mode is activated. Observe the additional information in the operating instructions of the room console. Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
4.1.3 System Check ❒ Check that the main fuse for the boiler has a sufficient rated amperage (16A ) ➥ If a safety overload switch is used, it should be a type with 16A. Operating Instructions Lambdatronic S 3200 | B0361214_en...
Installer / Service Releases parameters to adjust the controller to the system components (if configured). All the parameters shown in these operating instructions are available. Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Page 30
For description see “ Lambdatronic S 3200 Energy Systems” brochure Variant 1 Variants 2 and 5 Multiple house diagrams Variant 3 Variant 4 Slave boiler for boiler sequence control Only for systems in the cascade! Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Page 31
Solar collector 01 installed YES / NO ❒ The “remote control XX installed” parameter should be set to “YES” if any of the three remote controls shown is used for the respective heating circuit. Operating Instructions Lambdatronic S 3200 | B0361214_en...
When starting up for the first time ensure that the combustion chamber heats up slow‐ ly. Information on safety and implementation in the operating instructions of the boiler must be observed. NOTICE! See chapter on Initial Startup in the assembly instructions of the boiler Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Heating 08:15 Boiler 60 °C Lambdatronic S 3200 controls the combustion according to the boiler setpoints that Flue gas 180 °C have been set. If the criteria for "Heating" status are not reached within a specified time, the boiler switches to "Off" status.
(with autom. igni‐ criteria for heating status within a specified time. tion) Heating The Lambdatronic S 3200 controls combustion according to the boiler setpoints. Slumber Very low power consumption. When the boiler temperature setpoint is exceeded by a specified value, the boiler goes to "Slumber"...
(heating circuits, DHW tanks ...). The structure of the time menu and the procedure for changing the times are always the same. Example - Setting times for heating circuit 01: In the "Heating" menu -> "Times": Operating Instructions Lambdatronic S 3200 | B0361214_en...
Then carry out the same process with the start time. After the enter key has been pressed repeatedly, the changes are adopted and the display returns to the pre‐ vious menu. Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Description Desired room temperature during 20°C Room temperature during heating mode (only with remote control) heating mode Desired room temperature during 16°C Room temperature during setback mode (only with remote control) setback mode Operating Instructions Lambdatronic S 3200 | B0361214_en...
If the room temperature or the flow temperature is lower than the set val‐ ue, the heating circuit pump will be switched on. 5.1.3 Heating times of the heating circuits Heating circuit 01 ... 18 ⇨ See "Setting times" [page 35] Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
If DHW tank 1 is positioned in front of the network mixer, it should not af‐ don't look at DHW tank 01 fect the temperature control of the remote line, therefore this parameter should be set to YES. NOTE: Parameters for heating circuit 2 only! Operating Instructions Lambdatronic S 3200 | B0361214_en...
If heating up program 7 is active, the selected heating circuit is adjusted to gram 7 the specified flow temperature. Heating up programs Heating up program 2: Heating up program 1: Heating up program 3: Heating up program 4: Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
1 on relevant module) (0 = core module) Use room temperature sensor input If room thermostats are used instead of room temperature sensors, this for room thermostat parameter must be set to YES. Operating Instructions Lambdatronic S 3200 | B0361214_en...
Initial value of DHW tank loading. The boiler temperature must be higher tween boiler and DHW tank is than the DHW tank temperature by this value so that the DHW tank load‐ ing process begins. (Only for systems without storage tanks) Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Bus address of the sensors and pumps used. tank 1 ⇨ See "Setting the module address" [page 20] Which sensor is used for solar refer‐ ence DHW tank 1 Which pump is used for DHW tank 1 Operating Instructions Lambdatronic S 3200 | B0361214_en...
Maximum DHW tank pump speed 100% If you need to limit the maximum speed of the DHW tank pump for system‐ ic reasons, you can do so by adjusting this parameter. Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
DFL: Flow-through of the solar panel system Today: Heat quantity that has been supplied by the solar panel system to‐ Total: heat quantity that has been supplied since activation of the solar panel system Operating Instructions Lambdatronic S 3200 | B0361214_en...
Storage tank bottom plus the set value produces the desired temperature tom differential of the collector return. If the collector return is too high, the storage tank pump speed is reduced. Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
DHW tank charging. Solar charging to which store Defines the storage tank to which the solar charging takes place. Operating Instructions Lambdatronic S 3200 | B0361214_en...
Page 50
Basic setting for the sensor type used: sensor? NO: Solar sensor - Froling YES: Sensor PT1000 Collector pump control Kp value 1.00 Control parameter for collector pump Collector pumps control Tn value 300s Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Bus addresses of the sensors used, depending on the system ⇨ See "Setting the module address" [page 20] Is an external flow through counter If an external volume flow sensor is used in the collector return, set this used parameter to “YES”. Operating Instructions Lambdatronic S 3200 | B0361214_en...
Top store temp. when the start-up 60°C If the temperature set is exceeded at sensor 0.1 the start relief valve relief valve switches to bottom store switches to bottom storage tank Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Page 53
Store charge is 0% at the following 30°C If the average temperature in the storage tank is less than the specified temperature (absolute value) value, the storage tank has a charge of 0%. Operating Instructions Lambdatronic S 3200 | B0361214_en...
Which sensor is used for storage tank sensor 3 Which sensor is used for middle storage tank Which sensor is used for bottom storage tank Which pump is used for the storage tank Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Invert pump outlet for store relief If the valve switches incorrectly, the way it is controlled can be adjusted valve using this parameter. Operating Instructions Lambdatronic S 3200 | B0361214_en...
Minimum boiler temperature to re‐ 65°C The pumps are activated at this boiler temperature. (Hysteresis 2°C) lease all pumps Minimum return temperature 60°C The minimum temperature required of the return to the boiler. Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
(1 – RTU / 2 – ASCII) Set hours since last maintenance to To reset the counter “Hours since last maintenance”, this parame‐ ter must be set to "YES”. After the has been reset, the parameter jumps to "NO”. Operating Instructions Lambdatronic S 3200 | B0361214_en...
The switching back of the isolating valve is delayed by the specified time. Standby boiler delivery temperature 95°C If the standby boiler exceeds the specified temperature, the isolating valve switches and skims the boiler (only with hydraulic system 3) Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
230V. If the valve switches incorrectly, this parameter can be adjusted. Which second boiler is installed? Oil boil‐ Boiler type of the secondary boiler: - OIL BOILER - GAS HEATER - MANUALLY FED - AUT. FED - GAS BOILER Burner relays Operating Instructions Lambdatronic S 3200 | B0361214_en...
Maximum ign. duration 15 m Specifies how long the ignition procedure should last. "Heating" status must be reached within this time. Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Return temperature setpoint 50°C Note the information on multiple house diagrams in the “Lambdatronic S at feeder 1 3200 energy systems" documents. Return temperature setpoint 50°C at feeder 2 Operating Instructions Lambdatronic S 3200 | B0361214_en...
Maximum speed for feeder pump 1 100% If you need to limit the maximum speed of the storage tank pump for sys‐ temic reasons, you can do so by adjusting this parameter. Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Temperature settings for regulating range of the differential temperature source regulating output. Maximum temperature for 100°C The standard settings of 10°C or 100°C are selected so that the values in heat sink normal operation stay outside a limit. Operating Instructions Lambdatronic S 3200 | B0361214_en...
Which sensor is used for the heat sink 3200 energy systems" documents. Sensor monitoring If relatively low temperatures (< 5°C) occur when using the diff. controller, setting the parameter to “NO” suppresses the error message Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Circulation pump run-on 300s Parameter only when a flow valve is used! If the flow valve does not register any more flow, the circulation pump car‐ ries on running for the time set. Operating Instructions Lambdatronic S 3200 | B0361214_en...
Maximum speed of the circulation 100% If you need to limit the maximum speed of the circulation pump for system‐ pump ic reasons, you can do so by adjusting this parameter. Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
1% - 100% ... manual, with corresponding % value ON value: 0 A 0% Pump 1 on core module A 0% Pump 0.1 A 0% Pump 0.2 A 0% Pump 7.1 A 0% Pump 7.2 A 0% Operating Instructions Lambdatronic S 3200 | B0361214_en...
The parameters displayed vary depending on the configuration. Hi-limit stat input E-stop input A … Automatic Boiler enable -A 0 … Automatic, OFF -A 1 … Automatic, ON 0... Manual, OFF 1 ... Manual, ON Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Minimum boiler temperature to re‐ 65°C The pumps are activated at this boiler temperature. (Hysteresis 2°C) lease all pumps Minimum return temperature 60°C The minimum temperature required of the return to the boiler. Operating Instructions Lambdatronic S 3200 | B0361214_en...
100% = spray valve active for the specified time 75% = spray valve active for 15 sec and 5 sec pause Flue gas condenser Shows the current values. Heating: 0 min Washing processes: 0 Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Maximum ign. duration 15 m Specifies how long the ignition procedure should last. "Heating" status must be reached within this time. Operating Instructions Lambdatronic S 3200 | B0361214_en...
If the residual oxygen content at "Heating" status rises above this value, which it switches to SHUTDOWN after the maximum heating up time has elapsed the control switches to status "Off" status. Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Broadband probe heating current 0.00A Display of the current values for the relevant broadband probe parameter Broadband probe heating voltage 0.00V Broadband probe Nernst 0.000V voltage Broadband probe pump current 0.000m Broadband probe internal resistance Operating Instructions Lambdatronic S 3200 | B0361214_en...
Page 74
❒ Set parameter to "YES" and press the enter key ➥ Automatic calibration of the broadband probe begins ➥ Once calibration is complete the parameter is automatically set to "NO" and the broadband probe is ready for use Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
"YES”. After the has been reset, the parameter jumps to "NO”. 5.12.2 Current values Parameter Description Boiler temperature 77°C Display of the current values for the relevant parameter. Flue gas temperature 210°C Flue gas setpoint 212°C Boiler control variable Operating Instructions Lambdatronic S 3200 | B0361214_en...
The display of the parameters varies depending on the system set. Which sensor is used for bottom storage tank Note the information on hydraulic systems in the "Lambdatronic S 3200 energy systems" documents. Which pump is used for the storage tank...
7 HEATING SYSTEM: Touch display with address 1 is allo‐ None Allocates the relevant control (address 1 - 7) to a particular heating circuit. cated to the following heating circuit: Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
In addition to the storage tank graphic, the storage tank top, middle (if present) and bottom temperatures are displayed. ET … external temperature BT … boiler temperature RT … room temperature (on RBG 3200 BT is replaced with RT) DT … DHW temperature Operating Instructions Lambdatronic S 3200 | B0361214_en...
(Only with service code). 5.12.12 Current user level ⇨ See "Changing the operating level" [page 28] Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Menu overview and parameters Menu - System 5.12.13 System type ⇨ See "Setting the system type" [page 29] Operating Instructions Lambdatronic S 3200 | B0361214_en...
The same functions that apply with PDM apply to the parameter values with 0-10V. The only difference is that instead of pulse duration modulation, a 0-10V signal is used to control the pump. Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
6.1 Procedure for fault messages When a fault occurs: ▪ The status LED flashes red or orange ▪ The display shows all the current fault messages and the warning symbol in the status line Operating Instructions Lambdatronic S 3200 | B0361214_en...
Page 84
If a fault has various causes or the cause can be resolved in vari‐ ous ways, you can scroll through with the navigation keys. Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Below the heating circuit number it notes the heating area, for which this heating cir‐ cuit is used. The relevant connected unit should be noted next to the pumps or sen‐ sors. Example: Module address = 2; Operating Instructions Lambdatronic S 3200 | B0361214_en...
Page 86
Sensor 2.4 Heating circuit module Sensor 2.5 Sensor 2.6 Bus cable correctly connected (see “Connecting the bus cable”)) Final check Addressing correctly carried out and recorded Jumper placed at the last module Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com...
Page 87
Menu structure - Lambdatronic S3200 Operating Instructions Lambdatronic S 3200 | B0361214_en...