Unit Identification - Carrier 45J Installation, Start-Up And Service Instructions Manual

Fan powered variable air volume terminals
Table of Contents

Advertisement

Fig. 2 — Series Flow Unit (45K Shown)
Fig. 3 — Parallel Fan Unit (45J Shown)
The 45J,M units are standard fan powered terminal units. The
45K,N units are quiet fan powered terminal units. The 45Q,R
units are low profile fan powered terminal units.
CONTROL OFFERINGS
Each 45J, 45K, 45M, 45N, 45Q, 45R unit is supplied with a
flow probe as a standard feature. This probe offers a flow aver-
aging capability and results in flow sensing capacity equal to any
competitive unit.
Control options include VAV, VVT, analog electronic, and
pressure-independent pneumatic.
Pneumatic controls are available with linear actuators and
single-function or multi-function controller. The multi-function
controller provides a simple switchover from normally open to
normally closed applications.
Electronic control units feature a factory-installed enclosure
that provides easy access for field connections.
STORAGE AND HANDLING
Inspect for damage upon receipt. Shipping damage claims
should be filed with shipper at time of delivery. Store in a
clean, dry, and covered location. Do not stack units. When
unpacking units, care should be taken that the inlet collars
and externally mounted components do not become damaged.
Do not lift units using collars, sensors, or externally mounted
components as handles. If a unit is supplied with electric or
hot water heat, care should be taken to prevent damage to
these devices. Do not lay uncrated units on end or sides. Do
not stack uncrated units over 6 ft high. Handle with care. Do
not handle control boxes by tubing connections or other ex-
ternal attachments. Tables 1-7 shows component weights.
INITIAL INSPECTION
Once items have been removed from packing, check careful-
ly for damage to duct connections, coils, or controls. File dam-
age claim immediately with transportation agency and notify
Carrier.
NOTE: Remove all packaging material and foreign material
from unit and ensure the blower wheel moves freely before
installation. Units are shipped with cardboard in both sides of
the fan inlet that MUST be removed.

Unit Identification

Each unit has 2 main labels attached to the casing. The FAN
UNIT label (Fig. 4) lists the model number, supply voltage re-
quirements, motor horsepower and overcurrent protection re-
quirements. The AIRFLOW label (Fig. 5) lists the model num-
ber, unit size, factory order number and location. The location
"tag" indicates where the unit is intended for installation. There
may be other labels attached to the unit, as options or codes may
require. Read all labels on a typical unit before attempting instal-
lation. Control boxes are assembled as indicated on the identifi-
cation label.
Contact your local Carrier representative for more in-
formation.
45N
5 — 12
MODEL NO
277
MOTOR
VOLT
1/2
HP
480
HEAT
VOLT
12.0
KW
FPB—313
TAG:
MOTOR(S) ARE THERMALLY PROTECTED
MIN. SUPPLY CIRCUIT AMPS
MAX. FUSE OR HACR CIRCUIT BREAKERS
MAX. OUTLET AIR TEMPERATURE 200 F
UNIT DESIGNED TO OPERATE AT NO LESS THAN 0.2 IWG STATIC PRESSURE.
ZERO CLEARANCE FROM UNIT, CONNECTED DUCT AND/OR PLENUM
TO COMBUSTIBLE MATERIAL.
Fig. 4 — Fan Unit Label
599049
ITEM:
ORDER:
45J
MODEL:
480
LINE VLT:
PH:
01
STEP:
CTL VOLT:
5.60
MIN CIR AMP:
MAX. FUSE OR HACR CIRCUIT BREAKERS
MIN WIRE SIZE
(COPPER CONDUCTORS ONLY):
(SUITABLE FOR AT LEAST 75 DEGREES CENT.)
VAV – 05 – 01
TAG:
Fig. 5 — Airflow Label
2
FAN UNIT
014
10 579600
C
CODE
60
1
PHASE
HZ
3.110
FLA(EA)
60
3
HZ
HZ
PHASE
14.43
AMPS
21.920
REPLACEMENT LINE FUSE
25.000
25 AMP 600V
AMPS
AIR
DUCT HEATER
UP
FLOW
010
C – 599049 – 10
REV:
SN:
12 X 10
0375
DUCT SIZE:
MIN FPM:
03
60
2.50
3.00
HZ:
KW:
AMP:
24
50
CTL VA:
15 AMP 600V
INTERNAL FUSE
15.00
AMP
12AWG
REV: