1. General description

The CCM 1010 contact closure multiplexer system
can transmit eight independent contact closure
signals unidirectionally over either one optical fiber
or a serial data link (RS-232). A CCM 1010 TX/RX
combination uses an optical wavelength of 850 nm
over multimode fiber.
Front panel LEDs indicate DC power good, correct
transmission
framing
synchronisation.
CCM 1010 equipment comes in the form of rack-
mountable 7TE modules to be slotted into a TKH
Security MC 11 or similar power supply cabinet, or
as stand-alone units (option /SA) needing separate
power supplies PSA 12 DC.

2. Indications and connectors

The CCM's front panel indications and connectors
are listed in table 1 below.
CCM TX
o
(optical connector)
o
8xCC (37-pin conn.)
Indicator LEDs
*DC
*FR
CCM RX
o
(optical connector)
o
8xCC (37-pin conn.)
Indicator LEDs
*DC
*SYNC
Table 1. CCM front panel features

3. Installation instructions

3.1 General
- Insert the units into an appropriate MC 11 or
similar power supply cabinet (and/or connect stand-
alone units to their power supplies) and connect
appropriate cabling. Pin assignments are listed in
section 5.
© Siqura 2017
Version 082102-1g
CCM 1010 (MW10)
CCM 1010
USER MANUAL
and
correct
receiver
optical out
CC inputs, data out
DC power good
signal framing OK
optical in
CC outputs, data in
DC power good
input signal sync OK
CCM TX
DC
FR
37/19
8xCC
20/1
Figure 1. Front panel features of the CCM
1010 TX (left) and RX
- After switching on the system, check whether all
LEDs glow green. If the FR LED on the CCM TX
is red, that unit is faulty. If the SYNC LED on the
RX lights red while the FR LED glows green,
check the optical link first.
3.2 Link type
The unit tries to establish and use a link type based
on link input measurements (default autodetect
mode; it holds on to an interface as long as signal is
present). To permanently select either the optical or
the RS-232 link, internal dip switches can be set.
To access these switches, take out the front panel
Phillips head screws indicated in figure 1 and slide
out the front panel/circuit board assembly. Dip
switches S1/S2 select between autodetect, the serial
link and the optical link (see figure 2 and table 2).
CCM RX
DC
SYNC
37/19
8xCC
20/1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CCM 1010 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Siqura CCM 1010

  • Page 1 The CCM 1010 contact closure multiplexer system can transmit eight independent contact closure SYNC signals unidirectionally over either one optical fiber or a serial data link (RS-232). A CCM 1010 TX/RX combination uses an optical wavelength of 850 nm 37/19 37/19 over multimode fiber.
  • Page 2 CC2 out A CC2 out B CC1 out A CC1 out B not used Table 3. D37 pin assignments of CCM 1010 TX (pins 1-9) and RX (pins 11-37). GND pins are the same for both.
  • Page 3 Interface detect poll that this unit be installed in locations accessible to trained service personnel only. Optical Siqura assumes no liability for the customer’s failure to Wavelength comply with any of these safety requirements. Fiber type multimode (50/62.5) TX output power RX min.
  • Page 4 Electrostatic discharge (ESD) can damage or destroy Warning: Operation of this equipment in a residential electronic components. Proper precautions should be environment could cause radio interference. taken against ESD when opening the equipment. This device has been tested and found to meet the CE regulations relating to EMC and complies with the limits SELV: conforming to IEC 60950-1, <...

Table of Contents