Buderus Logamax plus Service Manual page 15

Gas wallhung boiler
Hide thumbs Also See for Logamax plus:
Table of Contents

Advertisement

1H
is flashing.
Cumbustion chamber temperature sensor
ber (pump runs continuously)
Control Step
1.
Check if combustion chamber NTC
damaged or not and the position.
B Switch off the appliance.
B Pull the NTC cables out.
B Measure NTC resistance.
Are the values correct ? (see NTC
values)
2.
Check if cable damaged or not.
B Switch off the appliance.
B In case of NTC is cahnged :
- Pull the NTC cables out.
- Measure NTC resistance.
- Reconnect the NTC cable.
B Pull out the 20 poled connector on
control unit.
B Measure the NTC resistance
directly on 20 poled connector.
Are the measured values on NTC
and cocnector different ?
3.
Is there any blockage on flue gas
pipe?
4.
Is the correct MAP (fan speed) value
according flue gas pipe length
choosen ?
5.
Is fan running correct ?
GB012 - 25K
1)
is defect, not detected or overheating in cumbustion cham-
Action
yes:
B Check the cable connection.
1H failure still exist ? -->2.
no:
B Change the NTC.
B Connect the cable.
B Switch on the appliance.
1H failure still exist ? -->2.
yes:
B Change the cable harness.
B Switch on the appliance.
1H failure still exist ? -->3.
no:
-->3.
yes:
B Remove the blockage.
1H failure still exist ? -->4.
no:
-->4.
no:
B Adjust correct MAP value according flue gas pipe
length and diameter. See capitel 7.2.
1H failure still exist ? -->5.
yes:
-->5.
no:
B Change the fan.
1H failure still exist ? -->6.
yes:
-->6.
Failures / Errors
3
15