Carrier 50HT-A07 Installation Instructions Manual page 21

Single package rooftop cooling only size 07 with puron refrigerant
Table of Contents

Advertisement

Smoke Detector Sensor
Fig. 35 - - Typical Supply Air Smoke Detector Sensor
Location
Return Air without Economizer — The sampling tube is
located across the return air opening on the unit basepan.
See Fig. 36. The holes in the sampling tube face
downward, into the return air stream. The sampling tube is
connected via tubing to the return air sensor that is
mounted on a bracket high on the partition between return
filter and controller location. (This sensor is shipped in a
flat- - mounting location. Installation requires that this
sensor be relocated to its operating location and the tubing
to the sampling tube be connected. See "Completing
Installation of Return Air Smoke Sensor:" for details.)
Return Air Detector Sampling Tube
*RA detector must be moved from shipping position to operating position by installer
Fig. 36 - - Typical Return Air Detector Location
C08245
Return Air Detector module
(shipping position shown)*
Controller module
C07307
Return Air with Economizer — The sampling tube is
inserted through the side plates of the economizer
housing, placing it across the return air opening on the
unit basepan. See Fig. 37. The holes in the sampling tube
face downward, into the return air stream. The sampling
tube is connected via tubing to the return air sensor that is
mounted on a bracket high on the partition between return
filter and controller location. (This sensor is shipped in a
flat- - mounting location. Installation requires that this
sensor be relocated to its operating location and the tubing
to the sampling tube be connected. See the following
installation procedure.)
Fig. 37 - - Return Air Sampling Tube Location
Completing Installation of Return Air Smoke
Sensor:
1. Unscrew the two screws holding the Return Air
Sensor detector plate. See Fig. 39. Save the screws.
2. Remove the Return Air Sensor and its detector plate.
3. Rotate the detector plate so the sensor is facing out-
wards and the sampling tube connection is on the bot-
tom. See Fig. 40 and Fig. 38.
4. Screw the sensor and detector plate into its operating
position using screws from Step 1. Make sure the
sampling tube connection is on the bottom and the ex-
haust tube is on the top. See Fig. 40.
21
Return Air
Sampling Tube
C08129