7 After tube contraction work is completed, wrap it with
the insulation tape to finish.
CAUTION
• Make sure that the connection parts are not exposed
to outside.
• Be sure to use insulation tape and a contraction tube
made of approved reinforced insulating materials that
have the same level of withstand voltage with the
power cable. (Comply with the local regulations on
extensions.)
WARNING
• In case of extending the electric wire, please DO NOT
use a round-shaped Pressing socket.
– Incomplete wire connections can cause electric shock
or a fire.
Step 16 Setting additional functions
of wired remote control
Automatic Air-Volume (only for ACMNDKH)
When DPM is installed, Automatic Air-Volume function
cannot be performed simultaneously for all indoor units.
Automatic Air-Volume function must be performed for
each indoor unit with the wired remote control attached.
With its BLDC motor, you can use smart adjust the indoor
unit fan speed depending on the installation condition.
If the external static pressure is high so that the duct
becomes longer or if the external static pressure is low
so that the duct becomes shorter, Using the Automatic
Air-Volume function,the volume of exhaust air has been
adjusted to the rated volume flow rate automatically.
Insulation tape
Performing the Automatic Air-Volume function.
• Check the air conditioning unit stop.
Press the Power button to stop the air conditioner
• Go to Service setting mode with remote controller.
1 Press the
2 Press the
3 Press the
4 Press the
5 Select mode No. 8.2 , and set to "1".
6 Press the
7 Press the
SEG Used
5
6
1 2 3
Main Menu Sub-menu
and
buttons at the same time for more
than 3 seconds and then a Main menu will be displayed.
/
button to select
button to enter a Sub-menu setting screen.
/
button to select
button to enter a automatic air-volume setting screen.
/
button to select 1 to enable automatic
air-volume operation.
/
button to select 3 and then press
button to enter input voltage.
/
button to select 1~3 to set voltage.
(1 : 220V, 2 : 230V, 3 : 240V)
4
and then press
and then press