Datalogic SG4 Instruction Manual

Datalogic SG4 Instruction Manual

Ethernet adaptor for sg4 extended light curtain series
Hide thumbs Also See for SG4:

Advertisement

Quick Links

SG4 Dongle
Ethernet Adaptor for SG4 Extended Light Curtain Series
ISTRUCTION MANUAL
SG4E: Safety Light Curtain of SG4 Extended series.
SG Extended GUI: Graphic User Interface for personal computer for SG4E
Series Light Curtains.
CLONING
SG-Dongle can download SG4E ACM configuration from SG4E then
upload it to other Light Curtains with same product code. That's for backup
purposes in case of Light Curtain substitution after damage or series
configuration of several ESPEs with the same final function.
Step 1: Configuration Backup
Connect SG4-Dongle to source Sg4E as shown in Connection section of this
manual.
Hold
button till
indication appears on display.
Backup is done when DL led stops blinking (Fig. 1)
Fig. 1 Configuration download procedure
Step 2: Configuration Restore
Connect SG4-Dongle to destination Sg4E as shown in Connection section of
this manual.
Important: destination Sg4E must have the same product code of source
one.
Hold
button till
indication appears on display.
Restore is done when UL led stops blinking (Fig. 2)
Fig. 2 Configuration Download procedure
After a successful upload SG4-Dongle stores a configuration report and
shows the number of saved report.
A maximum of ten consecutive upload are allowed, then user must
download configuration reports by means of SG Extended User Interface.
After upload, configuration remains stored in SG4 Dongle: it's possible to upload
the same configuration to other light curtains (a new report is generated for each
upload).
Step 3: Download report and check Light Curtain
configuration
Connect SG4-Dongle to Ethernet and Power as shown in Connection
section of this manual (cfr. SG4 Dongle Standalone Connection).
In SG Extended GUI Download all reports stored in SG4-Dongle
Each configuration reports shows the Light Curtain Serial Number which the
corresponding configuration has been uploaded to and all the configuration
parameters.
Carefully check all the configured Light Curtains are
operating according to downloaded reports before
restoring normal plant operation.
To erase not relevant or already downloaded Safery Reports hold
button till
indication appears on display.
OFFLINE CONFIGURATION
SG-Dongle can store SG4E ACM configuration from SG Extended GUI
then upload it to one or more SG4E Light Curtains compatibles with
configuration parameters. That's useful for configuration of one or more SG4E
Light Curtains when no Ethernet connection is available on controlled
machinery.
Step 1: Store ACM configuration on SG4-Dongle
Connect SG4-Dongle to Ethernet and Power as shown in Connection
section of this manual (cfr. SG4 Dongle Standalone Connection).
In SG Extended GUI Choose "Safety System Configuration" to begin off-line
configuration.
Compose an SG4E System by dragging devices from catalogue with the
proper product code. (up to a 3 unit cascade configuration can be stored on
Sg4-Dongle)
Important: be sure to select the right SG4E product code according to
the device the configuration is going to.
A wrong selection will lead to a failure in device upload.
Step 2: Upload configuration to SG4E
Connect SG4-Dongle to destination Sg4E as shown in Connection section of
this manual.
Hold
button till
indication appears on display.
After a successful upload SG4-Dongle stores a configuration report. A
maximum of ten consecutive upload are allowed, then user must
download configuration reports by means of SG Extended GUI.
After upload, configuration remains stored in SG4 Dongle: it's possible to
upload the same configuration to other light curtains (a new report is
generated for each upload).
Step 3: Download report and check Light Curtain
configuration
Connect SG4-Dongle to Ethernet and Power as shown in Connection
section of this manual (cfr. SG4 Dongle Standalone Connection)
In SG4 UI Download all reports stored in SG4-Dongle
Each configuration reports shows the Light Curtain Serial Number which the
corresponding configuration has been uploaded to and all the configuration
parameters.
Carefully check all the configured Light Curtains are
operating according to downloaded reports before
restoring normal plant operation.
ERROR LOGGING
When connected to an SG4E System, SG4 Dongle can log light curtain
errors: detailed error information is saved on SG4 Dongle memory that can be
retrieved with the help of SG Extended GUI. That's useful for diagnostic
purposes on randomic light curtains lockout.
Only ACM configured SG4E Systems can be logged.
SG4 Dongle saves one log item each time the connected SG4E System locks
into a noncritical Failure Lockout. Maximum number of Log items depends
from cascade topology: 7 items for 3 unit cascades, 11 items for 2 unit
cascades, 23 items for single unit cascade.
When SG4E Dongle is moved from one SG4E System to a different one
actual log is erased and a new log initialized. Same happens after a change
of SG4E System configuration.
Connect SG4-Dongle to Ethernet and Power as shown in Connection
section of this manual (cfr. SG4 Dongle Standalone Connection).
In SG4 UI Choose "Open Safety System Log form Device" to download and
visualize all Logs stored in SG4 Dongle.
Select SG Dongle device to visualize the contained "Safety system log".
A Safety system log contains
 A Safety system report with detailed configuration of loggeg SG4E System
 One or more log item with detailed error information.
ADVANCED USER INTERFACE
When connected to an SG4E Light Curtain in operations, SG4-Dongle shows
detailed light curtain status information on 7-seg display.
See "Diagnostics" Chapter of SG4E Manual for more details about UI
messages.
FAILURE MESSAGGES
Failure on OSSDs
Failure on Microprocessors
Failure on Optics
Failure on EDM
Failure on Restart
Communication Failure
Failure on BCM configuration
Failure on ACM configuration
Failure on Muting Lamp
STATUS MESSAGGES
Light curtain in Alignment Mode, Correct Alignment
Light curtain in Alignment Mode, Not Aligned
Light curtain in Alignment Mode, last beam not aligned
Light curtain in Alignment Mode, first beam not aligned
Light curtain in Alignment Mode, intermediate beam not
aligned
Light curtain in Interlock, activate RESTART line
Advanced Configuration from SG Extended GUI
running
Muting function active
Light curtain is ready to accept override request
Override function active
Wrong input signal sequence on override request
Blanking zone constraints not respected
Blanking function active

Advertisement

loading

Summary of Contents for Datalogic SG4

  • Page 1 In SG Extended GUI Choose “Safety System Configuration” to begin off-line Failure on BCM configuration errors: detailed error information is saved on SG4 Dongle memory that can be configuration. retrieved with the help of SG Extended GUI. That’s useful for diagnostic Failure on ACM configuration purposes on randomic light curtains lockout.