Vent Pipe Connection To Blower; Coupling Installations According To Vent Sizes - Lochinvar PVL 07575 Installation And Operating Manual

Power vented gas water heaters series 210/211
Table of Contents

Advertisement

3 in. MIN.
LENGTH
A VENT USED IN A
SPECIAL VENTING
SYSTEM WITH POSITIVE
VENT PRESSURE AND
PASSING THROUGH A
ROOF SHALL EXTEND AT
LEAST 18 in. ABOVE THE
HIGHEST POINT WHERE
IT PASSES THROUGH THE
ROOF SURFACE AND ANY
OTHER OBSTRUCTION
WITHIN A HORIZONTAL
DISTANCE OF 18 in. .
A VERTICAL VENTING
SYSTEM MUST BE
SUPPORTED EVERY 5 ft. .
Figure 36.

Vent pipe connection to blower

1. The vent piping connects into the rubber coupling
located on the top of the blower assembly. This
coupling includes gear clamps to connect the venting
to the blower. These connections must be properly
seated and tightened to prevent the leakage of flue
gases into the area. See Figure 37 through Figure 39.
2. The water heater is supplied with a 3" rubber
coupling to accept the vent pipe and is required in all
installations. Do not attempt to connect the vent piping
directly to the blower without using the rubber coupling.
Note: Polypropylene vent systems require separate
adaptor.
3. Before installing clean and lightly sand the end of the
plastic vent piping that will connect into the rubber
coupling. For polypropylene vent systems follow
manufacturer's instructions.
4. Loosen the upper clamp on the rubber coupling and
insert the sanded end of the vent piping a full 1-1/4
in. . Do not use glue or sealant in the rubber coupling.
Check that there is no stress on the connection or the
vent piping that may be caused by twisting or bending.
5. Tighten the upper clamp so that the vent piping is
firmly secured in the coupling and is gas tight. Do not
over tighten or cause distortion of any of the parts.
Ensure the bottom of the rubber coupling is firmly
seated on the blower outlet and that the lower gear
clamp is also secure. Check to ensure there is no
distortion or movement of the clamped assembly once
it is completed.
6. If the outlet vent pipe is to be turned horizontally
directly off the blower, a 3 in. long section vent pipe
shall be used to connect the elbow to the rubber
coupling (see Figure 39). For heaters installed with
the option using the first 5 ft. being CPVC venting, the
first elbow is in addition to the 5 ft. rule (see "Venting").
100221773_2000189439_Rev. 01
TERMINATION
MAY BE 90°
ELBOW
18 in. OR
RODENT
SCREEN
ABOVE
ANTICIPATED
(INSTALL
INTO
SNOW LEVEL
ELBOW)
ROOF
LINE
www. lochinvar .com
CAUTION
Property Damage Hazard
• Do not overtighten the top and bottom gear clamps of the
rubber coupling.
• Do not apply solvent cement or silicone to the rubber
coupling connection.

Coupling installations according to vent sizes

* HEATERS
EQUIPPED WITH
THE 181° CONTROL
MUST USE CPVC
PIPING FOR
3" RUBBER
THE FIRST 5' OF
COUPLING
VENTING.
(SUPPLIED)
BLOWER
Figure 37.
* HEATERS
EQUIPPED WITH
THE 181° CONTROL
MUST USE CPVC
PIPING FOR
THE FIRST 5' OF
VENTING.
3" RUBBER
COUPLING
(SUPPLIED)
BLOWER
Figure 38.
3" VENT
PIPE*
(SUPPLIED)
3" VENT
PIPE*
(SUPPLIED)
BLOWER
* HEATERS
EQUIPPED WITH
THE 181° CONTROL
MUST USE CPVC
PIPING FOR
THE FIRST 5' OF
VENTING.
Figure 39.
3" VENT
PIPE
4" VENT
PIPE*
3"-4"
ADAPTER*
(FIELD
SUPPLIED)
3" VENT
PIPE*, 3 in.
MAX LENGTH
3" ELBOW
**(FIELD
SUPPLIED)
3" RUBBER
COUPLING
(SUPPLIED)
33

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pvn 07575Cvn075075Cvl075075

Table of Contents