DELUXE
1
Select location for installation.
PROGRAMMABLE
1"
THERMOSTATS
Quick Start Installation Manual
Cut
Models 9801i2 and 9825i2
1-1/2"
out
opening
1/2"
Remove 1/2" of insulation
from end of each wire
110-1183
Installation DOs and DON'Ts
8
Connect wiring between the thermostat and
equipment. For Model 9825i2 (2 heat / 2 cool;
DO
gas / electric).
• Shut off all power to system before installing.
Thermostat
TERMINAL DESIGNATIONS
• Read entire manual before installing.
C
R
• Make sure that all wiring conforms to
C
Y1
R
national and local codes.
Y1
E/W1 - 1st stage heating
E/W1
D
D
W2
W2
Y2
Y2
DO NOT
L
L
H
H O B G
9825
2
• Install on voltages greater than 30 VAC.
i
O
B
• Short jumper across terminals on the gas
G
valve or at the system control.
C
Terminal D and H - Please
R
refer to equipment manual
• Connect ground to any terminal in
Y1
for proper termination.
W1
this unit.
Equipment Wiring Terminals -
W2
Please refer to furnace
• Install on outside walls or in direct sunlight.
Y2
installation manual for
L
proper terminations.
G
B
O
Set the time. Hours and minutes are
DELUXE
3
set separately. An AM/PM indicator
PROGRAMMABLE
automatically changes based on the
THERMOSTATS
hour chosen.
Setup Wizard Quick Start Guide
Press Next.
Set Time
The Setup Wizard allows you to quickly step
(Hour)
through the setup process. This guide
12:00
PM
shows a typical setup for a basic heating
system. The screens you see depend on
Back
Next
thermostat model and your heating/cooling
configuration.
Set the date.
4
First, set the month. Press Next.
NOTE: Use the
or
button to select a list
Then, set the day. Press Next.
item or to change the value of a number.
Finally, set the year. Press Next.
Use the gray buttons below the display to
Set Date
choose No, Yes, Back, Next, Next Char or
(Month)
Accept when appropriate.
1/1/05
Back
Next
Choose the time format – 12-hour
Selecting Yes allows you to go
5
1
clock or 24-hour clock.
through the setup process.
Press Next.
Would You Like
To Run the
Select Time Format
Setup Wizard?
12hr
24hr
No
Yes
Back
Next
Choose either English, Español, or
2
To activate the Auto Daylight Saving
Français as the display language.
6
Time feature, choose either:
This can always be changed after
Standard (April – October), or
the Setup Wizard is complete.
Extended (March – November).
Press Next.
Press Next.
Select Language
English
Auto Adjust For DST?
Español
No
Français
Standard (Apr-Oct)
Extended (Mar-Nov)
Back
Next
Back
Next
2
3
Open the case with a screwdriver. Place in slot
and gently pry forward at all four locations.
a
b
2
1
3
4
9
10
Connect wiring between the thermostat and
equipment. For Model 9825i2 (2 heat / 2 cool;
heat pump with strip heat).
Thermostat
TERMINAL DESIGNATIONS
- 24VAC Common
C
- 24VAC Common
- 24VAC
R
- 24VAC
C
- 1st stage cooling
Y1
- 1st stage heating/cooling
R
Y1
E/W1 - Emergency heat
E/W1
- Dehumidify
D
- Dehumidify
D
- 2nd stage heating
W2
- 2nd stage heating
W2
- 2nd stage cooling
Y2
- 2nd stage cooling
Y2
L
- Not used
L
- System fault indicator
- Humidify
H
- Humidify
H O B G
9825
2
i
- Not used
O
- Cool active reversing valve
- Not used
B
- Heat active reversing valve
- Fan
G
- Fan
C
R
Terminal D and H - Please
Y1
refer to equipment manual
E
for proper termination.
W2
Equipment Wiring Terminals -
Y2
Please refer to heat pump
L
installation manual for
G
proper terminations.
B
If terminal E is not supplied,
O
add jumper across E/W1 and
W2 on the thermostat.
Select either the Fahrenheit or Celsius
7
11
temperature scale.
Press Next.
Select Temperature
Scale
°C
°F
Back
Next
Select the type of heating system that
8
will be used with the thermostat.
Press Next.
1st Stage Heat Equip
None
Furnace
Strip
Heat Pump
Back
Next
Auto changeover allows automatic
9
switching between heating and
cooling.
Make your selection. Press Next.
Enable
Auto Changeover?
No
Yes
Back
Next
Service reminders are available for:
10
Heat System, Heat Pump, Cool
System, Filter, UV Light and
Humidifier Pad. All can be set to OFF
or from 1 to 12 months.
Press Next.
Reminder To Service
Heat System In:
3
Mon
Back
Next
4
Mark mounting hole locations on wall.
Drill 3/16" holes at marked locations on wall.
Insert plastic anchors into holes.
Drill 3 / 16 holes
a
Mark mounting hole
locations on wall using
b
unit base as template.
Press anchors into holes until flush.
11
Connect wiring between the thermostat and
Connect wiring between the thermostat and
equipment. For Model 9825i2 (2 heat / 2 cool;
equipment. For Model 9825i2 (2 heat / 2 cool;
heat pump with furnace).
2 stage heat pump with strip heat).
Thermostat
TERMINAL DESIGNATIONS
Thermostat
TERMINAL DESIGNATIONS
C
- 24VAC Common
C
- 24VAC Common
R
- 24VAC
R
- 24VAC
C
C
Y1
- 1st stage heating/cooling
Y1
- 1st stage heating/cooling
R
R
Y1
Y1
E/W1 - Emergency heat
E/W1 - Emergency heat (strip)
E/W1
E/W1
D
- Dehumidify
D
- Dehumidify
D
D
W2
- 2nd stage heating
W2
- 2nd stage heating
W2
W2
Y2
- 2nd stage cooling
Y2
- 2nd stage cooling
Y2
Y2
L
L
L
- System fault indicator
L
- System fault indicator
H
- Humidify
H
- Humidify
H O B G
9825
2
H O B G
9825
2
i
i
O
- Cool active reversing valve
O
- Cool active reversing valve
B
- Heat active reversing valve
B
- Heat active reversing valve
G
- Fan
G
- Fan
C
C
R
Terminal D and H - Please
Terminal D and H - Please
R
Y1
refer to equipment manual
refer to equipment manual
Y1
E
for proper termination.
for proper termination.
E
W2
Equipment Wiring Terminals -
Equipment Wiring Terminals -
W2
Y2
Please refer to heat pump
Please refer to heat pump
Y2
L
installation manual for
installation manual for
L
G
proper terminations.
proper terminations.
G
B
If terminal E is not supplied,
B
O
add jumper across E/W1 and
O
W2 on the thermostat.
Contact information can be entered
DELUXE
at the factory. Talk to your
PROGRAMMABLE
Robertshaw sales representative
THERMOSTATS
about this feature.
Operational Mode Chart
To edit information: Use the
or
button to scroll through the character
list. Press Next Char to move to the
No 2nd
HVAC Mode
next character. Press Accept to move
to the next line, and finish editing.
Stage
is Emer
Set Contact Info
Outdoor
1st Stage
(Name)
Temperature
(2nd is na)
ABC HEATERS
123-555-2345
Next Char
Accept
< Low balance
E/W1
Between
E/W1
balance points
No sensor
3
Y1
E/W1
> High balance
E/W1
1. The 2nd stage is not used for heating when
the outdoor temperature is not between the
two balance points.
2. Standard and Add-On apply when the 2nd
stage is on. Y1 is either on (Standard) or off
(Add-On).
5
6
Align unit base over plastic anchors embedded
Connect wiring between the thermostat and
in wall and secure with the screws provided.
equipment. For Model 9801i2 (1 heat / 1 cool;
gas / electric).
Thermostat
H O B G
12
13
Connect wiring between the thermostat and the
Replace cover on thermostat. Turn on power
indoor sensor (9020i) and the outdoor sensor
to unit and proceed with programming
(9025i), if used. Use twisted pair wiring (22AWG
per instructions on the display or in the
minimum) with a maximum length of 300 feet
user's manual.
(or 100m).
2nd Stage is
2nd Stage is a
2nd Stage is a Furnace
Strip
Heat Pump
Heat Pump
Standard
2
Add-On
2
Only
4
1st
2nd
1st
2nd
1st
2nd
1st
2nd
W2
na
1
W2
na
1
W2
na
1
E/W1
na
1
Y1 +
W2
Y1 +
Y1 +
Y1
Y1
Y1
Y1
W2
2
only
2
W2
2
W2
Y1 +
W2
Y1 +
Y1 +
Y1
Y1
Y1
Y1
W2
2
only
2
W2
2
W2
Y1
na
1
Y1
na
1
Y1
na
1
Y1
na
1
3. When no sensor is present, the thermostat
behaves as if the outdoor temperature is
always between the balance points.
4. Heat Pump Only applies to the 9825i2 when
it is configured as Heat Pump in both 1st and
2nd stage.
7
Connect wiring between the thermostat and
equipment. For Model 9801i2 (1 heat / 1 cool;
heat pump with strip heat [emergency]).
TERMINAL DESIGNATIONS
TERMINAL DESIGNATIONS
Thermostat
C
- 24VAC Common
C
- 24VAC Common
R
- 24VAC
R
- 24VAC
Y1
- 1st stage cooling
C
Y1
- 1st stage heating/cooling
E/W1 - 1st stage heating
C
R
E/W1 - Emergency heat
R
Y1
D
- Dehumidify
Y1
D
- Dehumidify
E/W1
W2
- Not used
E/W1
W2
- Not used
D
Y2
- Not used
D
W2
Y2
- Not used
W2
Y2
L
- Not used
L
- System fault indicator
Y2
L
H
- Humidify
L
H
- Humidify
O
- Not used
O
- Cool active reversing valve
9801
2
H O B G
i
B
- Not used
9801
2
i
B
- Heat active reversing valve
G
- Fan
G
- Fan
Terminal D and H - Please
G
Terminal D and H - Please
G
refer to equipment manual
Y1
refer to equipment manual
Y1
for proper termination.
for proper termination.
R
R
Equipment Wiring Terminals -
E
Equipment Wiring Terminals -
W1
Please refer to furnace
Please refer to heat pump
C
installation manual for
C
installation manual for
proper terminations.
B
proper terminations.
O
Recycling Thermostat
If this thermostat REPLACES a thermostat that contains mercury,
DO NOT discard the old thermostat in the regular trash. Mercury
is harmful to humans and the environment. For this reason, do
not open, break, or crush the mercury cell. If mercury leaks from
a damaged cell, DO NOT touch or handle mercury with bare
hands. Use protective, non-absorbent gloves to place mercury
into a sealable container. Fill the container with sand or another
absorbent material and seal the container completely.
Return the mercury or mercury products, in a sealed container, to
Invensys Climate Controls or a local recycling center for proper
disposal. If you have any questions, call Robertshaw technical
support at 1-800-445-8299.
In U.S.:
Invensys Controls Americas
28C Leigh Fisher Blvd.
El Paso, TX 79906
Attn: Mercury Recycling Center
In Canada:
Invensys Controls Americas
3515 Laird Road - Unit #14
Mississauga, Ontario L5L 5Y7
Attn: Mercury Recycling Center
NOTES:
NOTES:
Controls Americas
515 South Promenade Avenue
Corona, CA 92879-1736
United States of America
Made in U.S.A
www.about-i-series .com
110-1183