Chapter 3 - Troubleshooting; General; All Leds Are Off; Alarm Led - TC Communications TC2200R User Manual

Multi-drop (bus) fiber optic modem
Table of Contents

Advertisement

General

Alarm conditions occur whenever an optical problem or "fault" condition is detected by the TC2200/2201.
Under normal operation, all LEDs should be lit, with the exception of either the "DTE" or "DCE" and
"ALARM" LEDs. The "BRD" and "RSP" LEDs will only light when there is activity on the bus.

All LEDs are Off

If no LEDs are lit on the unit, check the DC power supply, terminal block connector plug, and/or the power
source. If the problem persists, contact the Technical Support Department at TC Communications, Inc.

Alarm LED

When an alarm condition is detected, the Alarm LED will flash rapidly and one or more additional LED will
flash. The following fault conditions will cause the alarm to be triggered:
1. Optic signal lost from "RxA" or "RxB."
2. Optic signal is marginal, which causes invalid data packets to be received; either the "SynA" or "SynB"
LED will be flashing.
3. Optic overdrive can cause the "SynA" or "SynB" LED to flash while optic "A" and/or "B" still receives
a valid signal.
4. One or more of the front panel's DIP switches is in the Down position.
5. The Anti-Streaming function has been activated.

Optic Cable Types

Conventionally, fiber optic cable with yellow-colored insulation is used for Single Mode applications; gray
or orange-colored insulated cable is for Multimode use. If Multimode cable is used in a Single Mode
application, the test results could be erroneous and confusing.

Calculating the Loss on the Fiber

The fiber optic link and/or connectors are frequently the source of various problems. Check out the
connectors and the integrity of the link first. Ideally, the link should be calibrated for total loss after the
installation has been completed. This will accomplish two things: (1) it will verify that the total loss of the
link is within the loss budget of the device and (2) it will provide a benchmark for future testing. For example,
a system that has been tested as having 6dB total loss when installed and suddenly tests out as having a loss
of 10dB probably has a connector or link problem.
These are the reference values we use to calculate the loss on the fiber:
Multimode 850nm
Multimode 1310nm
Single Mode 1310nm
Single Mode 1550nm
*These numbers are listed for reference only. We recommend an OTDR reading be used to determine actual link loss.

Chapter 3 - Troubleshooting

:
:
:
:
3 dB loss per km on 62.5/125µm cable*
2 dB loss per km on 62.5/125µm cable*
0.5 dB loss per km on 9/125µm cable*
0.25 dB loss per km on 9/125µm cable*
- 13 -
TC2200R/S Bus
User's Manual
Rev. 2.2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tc2200sTc2201rTc2201s

Table of Contents