Mitsubishi Electric MXZ-4C36NAHZ Technical & Service Manual page 157

Split-type, heat pump air conditioners
Hide thumbs Also See for MXZ-4C36NAHZ:
Table of Contents

Advertisement

OPERATING PROCEDURE
9. Removing bypass valve coil (SV1) and bypass valve
Refer to the notes below.
10. Removing the high pressure switch (63H) and high pres-
sure sensor (63HS)
Refer to the notes below.
11. Removing the low pressure sensor (63LS)
Refer to the notes below.
12. Removing electronic expansion valve (LEV-A, LEV-B)
OCH573E
PHOTOS/FIGURES
Photo 11
Photo 12
Notes:
1. Recover refrigerant without spreading it in the air.
2. The welded part can be removed easily by removing
the right side panel.
3. When installing the following parts, cover it with a wet
cloth to prevent it from heating as the temperature
below, then braze the pipes so that the inside of pipes
are not oxidized;
cedure 10), 212°F [100°C] or more
-