Protec CIRRUS HYBRID User Manual

Protec CIRRUS HYBRID User Manual

Aspirating smoke detection systems
Hide thumbs Also See for CIRRUS HYBRID:

Advertisement

PROTEC CIRRUS HYBRID
ASPIRATING SMOKE
DETECTION SYSTEMS
USER MANUAL
Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND
+44 (0) 1282 717171
www.protec.co.uk
sales@protec.co.uk

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CIRRUS HYBRID and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Protec CIRRUS HYBRID

  • Page 1 PROTEC CIRRUS HYBRID ASPIRATING SMOKE DETECTION SYSTEMS USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND +44 (0) 1282 717171 www.protec.co.uk sales@protec.co.uk...
  • Page 2 Document Revision Details Issue Modification Detail Author Date Document Creation 15/11/15 N93-601-00 Issue 1 Page 2 of 25 © Protec Fire Detection PLC 2015...
  • Page 3: Table Of Contents

    Introduction ........................... 6 Cloud Chamber ..........................6 Scatter Chamber Detector ......................7 Hybrid ............................7 CIRRUS HYBRID GENERAL COMPONENT OVERVIEW ..............8 External Component Overview ..................... 8 LED Status Indication ........................8 Internal Component Overview ...................... 9 Front Door Assembly Component Overview ................10 Cirrus Hybrid Display ........................
  • Page 4 The policy of Protec Fire Detection plc is one of continuous improvement. As such we reserve the right to make changes to product specifications at any time and without prior notice. Errors and omissions excepted.
  • Page 5: Scope Of Document

    This document details the user information for the Protec Cirrus Hybrid Aspirating Smoke Detector with specific attention to the basic system operations of the product. The Protec Cirrus Hybrid Aspirating Smoke Detector has been designed and manufactured in the United Kingdom and complies fully with current standard dictating aspirating smoke detector design practice (EN54 parts 20).
  • Page 6: Cirrus Hybrid General

    The Cirrus Hybrid is a self-supervised system that continuously monitors for correct operation. Any problem is immediately reported on the front panel display, buzzer and the operation of a Fault relay. The Cirrus Hybrid locally stores fault data, background particle concentration and event data. These can be accessed from the Menus.
  • Page 7: Scatter Chamber Detector

    The scatter chamber detector in the Cirrus Hybrid is very sensitive, many times more than that of the point detector and so can be used in an aspirating system which has considerable dilution from clean areas.
  • Page 8: Cirrus Hybrid General Component Overview

    Product Manufacture Label Figure 4.1 Cirrus Hybrid External Components LED Status Indication Supply Heathy Fault Pre-Alarm Fire 1 to 3 Figure 4.2 Cirrus Hybrid LED Status Indication N93-601-00 Issue 1 Page 8 of 25 © Protec Fire Detection PLC 2015...
  • Page 9: Internal Component Overview

    Sample Inlet, Purge & Vacuum Outlet Unit Wall Fixing Points Front Door (Rear View) Label: Wiring Diagram Hybrid scanning unit only Figure 4.3 Cirrus Hybrid Internal Components N93-601-00 Issue 1 Page 9 of 25 © Protec Fire Detection PLC 2015...
  • Page 10: Front Door Assembly Component Overview

    Ribbon Cable to Cloud Chamber and Zone Scanning Unit Ethernet Connection TCPIP (RJ45) USB_B Computer Connection Camera Connection (RJ45) Touch Display Calibration Reset Button Figure 4.4 Cirrus Hybrid Front Door Assembly Components N93-601-00 Issue 1 Page 10 of 25 © Protec Fire Detection PLC 2015...
  • Page 11: Cirrus Hybrid Display

    Cirrus Hybrid Display The Cirrus Hybrid uses a touch screen for its display. There are no buttons other than those presented on the touch screen. The display is based on a scrolling webpage which initially shows the top of the page, representing the first page or screen, known as the Home Page.
  • Page 12: Access Code

    The default access code can be changed from the access code menu screen Providing the user access code has been correctly entered the user can begin to view and edit basic system functions of Cirrus Hybrid detector. N93-601-00 Issue 1 Page 12 of 25 ©...
  • Page 13: Home Page

    Providing ‘timezone’ is enabled, the home page will display indicate the pipe night mode is activated. Silence and reset The Cirrus Hybrid is fitted with an internal buzzer. The buzzer will sound when the unit is in Fault, Pre- alarm or Fire. Buzzer parameters...
  • Page 14: Setting The Date And Time

    Set the date by:  navigating the >> arrows to the correct year  navigating the > arrows to the correct month  clicking the correct day. N93-601-00 Issue 1 Page 14 of 25 © Protec Fire Detection PLC 2015...
  • Page 15: Viewing The Airflow & Fan Settings

    5% to 100%. The acceptable fault tolerance area is displayed on the dial in green; therefore any reading in the red area generates a fault. N93-601-00 Issue 1 Page 15 of 25 © Protec Fire Detection PLC 2015...
  • Page 16: Changing The User Access Code

    The network menu displays:  Protec Loop serial number.  Protec address for each pipe assigned by the Protec fire panel  IP address, Subnet Mask and Gateway either automatically assigned by network or manually inputted as a fixed address.
  • Page 17: Viewing The Event Log

    Click again to toggle between event log, realtime and historical graph. The Cirrus Hybrid stores all fire, faults and events in the event log. The event log can store a maxium of 256 events. In the user access level 16 latest events are viewable.
  • Page 18: Response To An Alarm

    Fire When a fire alarm condition is activated the Cirrus Hybrid unit will display the pipe text of the pipe in alarm and the fire alarm level (1, 2 or 3) in the ‘detector status’ list. The fire alarm level LED will illuminate and the buzzer will pulse (fast).
  • Page 19: Response To A Fault/S

    Check the device in fault is fitted correctly otherwise contact a Protec operative or a Protec distributor. Device Added A Cirrus Hybrid device has been added to the unit but the unit has not been commissioned to enable the device. The device will NOT detect fires.
  • Page 20: Cloud Chamber Led Fault

    The unit has detected that insufficient light is being received at the photodiode. User Action Contact a Protec operative or a Protec distributor. Water fill fault The unit has detected that the water fill value level reading out of range.
  • Page 21: Supply Fault

    6.22 Battery A monitored input set up for External Battery Fault has detected a fault. User Action Check the power supply equipment and wiring if the fault persists contact a Protec operative or a Protec distributor. N93-601-00 Issue 1 Page 21 of 25...
  • Page 22: Mains

    6.23 Mains A monitored input set up for Mains Fault has detected a fault. User Action Check the power supply equipment and wiring if the fault persists contact a Protec operative or a Protec distributor. 6.24 Pipe Scan Halted The pipe hold function forces a scanning unit to sample from the selected pipe. While unit is in this state it will display a ‘Pipe Scan Halted fault’, until the pipe hold function is disabled.
  • Page 23: Events

    Events The Cirrus Hybrid stores operational events within the internal memory ‘event log’. The following events are logged. Processor Fault The internal processor hardware has unexpectedly reset. Power Up The unit has powered up, occurring on first power, unstable supply voltage or after an undesired reset.
  • Page 24: Maintenance

    (<50% R.H) or high ambient temperature (>30C) conditions will increase the water usage. Periodic Checks and Maintenance The Cirrus Hybrid continuously adjusts its monitoring functions by means of feedback loops, ensuring a minimum of maintenance. To ensure continued correct operation, the system must be checked: ...
  • Page 25: Technical Specifications

    1.1A maximum at 24V (blower set to 100%, 4 Pipe Detector) Consumption Protec Algo-tec™ 6000 Loop Protocol Loop Isolator On board consult Protec DEL2110 for details Loop Quiescent Current 0.7mA Consumption Fault Contact Rated at 30 V maximum [Normally closed]...