Preset Single Register - Function Code 06; Preset Single Register Query; Preset Single Register Response; Loopback Test - Function Code 08 - ABB C1300 User Manual Supplement

Advanced circular chart recorder
Hide thumbs Also See for C1300:
Table of Contents

Advertisement

C1300
Advanced Circular Chart Recorder
5.4 Preset Single Register – Function Code 06

5.4.1 Preset Single Register Query

The preset single register allows the user to modify the contents of a holding register.
Note. Function codes 5, 6 and 16 are the only messages that are recognized as valid for broadcast.
Example – a preset single register request to write the value 500 to holding register address 121 (alarm trip A1) in slave 01 is shown
below.
Note. To write to a register, the register's offset address must be used, e.g. to write to register 121, the offset address 120(78H)
is transmitted.
Address
Function
01
06

5.4.2 Preset Single Register Response

The normal response to a preset single register request is to retransmit the query message after the register has been altered.
Example:
Address
Function
01
06
5.5 Loopback Test – Function Code 08

5.5.1 Loopback Test Query

The purpose of the loopback test is to test the Modbus system, it does not affect the content of the controller. Variations in the
response may indicate faults in the Modbus system. The information field contains 2 bytes for the designation of the diagnostic code
followed by 2 bytes to designate the action to be taken.
Example:
Address
Function
01
08
*These are considered to be the information fields for diagnostic mode.

5.5.2 Loopback Test Response

The response always echoes the query, only diagnostic code 0 (bytes 3 and 4) can be used.
Example:
Address
Function
01
08
*These are considered to be the information fields for diagnostic mode.
IM/C1300–MOD
Rev. C
Register Offset
High
Low
00
78
Register Offset
High
Low
00
78
Data Diagnostic Code
High
Low
00
00
Data Diagnostic Code
High
Low
00
00
Data Value
High
Low
01
F4
Data Value
High
Low
01
F4
Data*
Data*
A5
37
Data*
Data*
A5
37
5 Modbus Functions
Error Check Field
(CRC-16)
09
C4
Error Check Field
(CRC-16)
09
C4
Error Check Field
(CRC-16)
DA
8D
Error Check Field
(CRC-16)
DA
8D
11