Download Print this page

Honeywell K595 Installation Manual page 2

Advertisement

Binding
Prepare Binding with an E528.LX
Enter Service Parameter
Press and hold °F/°C
Mode
button
Press and release the
OFF/AUTO button
Press and release the
DISPLAY button
Release the °F/°C button
Set Room ID
Use OFF/AUTO and
UP/DOWN arrows to set
(PAR 10, 11, 12)
the Room ID in
parameters 10, 11 and 12.
Set RF Transmit Power
Set PAR 243 to desired
and RF Channel
RF Tx Power : RF
Channel
1
(PAR 243)
0dB : RF Channel 26
0dB : RF Channel 25
0dB : RF Channel 20
0dB : RF Channel 15
+3dB : RF Channel 26
+3dB : RF Channel 25
+3dB : RF Channel 20
+3dB : RF Channel 15
Only use the above RF
Channels to minimize
interference with other RF
sources such as WiFi
Access points.
Set PAN ID
Set PAR 242 to desired
PAN ID. The PAN ID can
(PAR 242)
be any value 1 to 255 and
must match the PAN ID
set into the PC-803 Edge
Router that manages this
room
RESET E528.LX
Set PAR 1 value=0 and
press DISPLAY button
Binding the K595
The binding process for the K595 is dependent on the
software. The K595 uses a reverse bind by first placing
the E528.LX/E529.LX into a "ready to teach" mode and
then initiating the bind from the K595 by pressing button
located under the blister cover.
1.
Insert 4 AA batteries in the battery back and connect it to the
unit if not already installed
2.
Enter the Service Parameter mode on the E528.LX/E529.LX
(as described above)
3.
Prepare the thermostat to bind the K595
Copyright 2013 INNCOM by Honeywell
• For the E528.LX
Screen displays P1
(parameter 1)
Use UP / DOWN arrow
button to scroll through
parameters (1–255). Use
OFF/AUTO to toggle
parameter value V.
Examples:
RoomID=2456
PAR 10=0 PAR 11=24
PAR 12=56
RoomID=24351
PAR 10=2 PAR 11=43
PAR 12=51
RoomID=406
PAR 10=0 PAR 11=4 PAR
12=6
Displayed PAR 243 Value
0F.h
0E.h
09.h
04.h
1F.h
1E.h
19.h
14.h
For multi-floor
installations, alternating
Note: The following table is for example only; the final
RF Channel between 25
and 26 can minimize
mapping will be determined by Application Engineering,
cross-floor interference
and they should be consulted on any questions.
between thermostat
radios.
PAR 242 is displayed in
hex 01.h (1) to FF.h (255)
Ex:
PAN ID=45 – PAR
242=2d.h
PAN ID=150 –PAR
242=96.h
Go to Parameter 15 (target address for teach
o
commands).
Press OFF/AUTO to view value.
o
Change value using UP/DOWN arrows.
o
Press OFF/AUTO to return to Parameter number mode
o
and scroll to Parameter 14.
Press OFF/Auto to view value of I/O Map.
o
Enter the number of the I/O Map (see Table1 below) to
o
be enabled in the bind.
For the E528.4G and e529.LX, go to Adr (target address for
teach commands)
Press OFF/AUTO to view value.
o
Change value using the UP/DOWN arrows, then press
o
DISPLAY.
Exit Adr using OFF/AUTO (display shows Pn6).
o
Press UP 5 times until Io (teach I/O Map) displays.
o
Press OFF/AUTO to view value and change it to the map
o
required for this installation (see Table 1 below).
Press the blue S1 switch on the K595 to initiate binding.
o
The K595 will broadcast a Bind Request message. If the
thermostat saw the Bind Request, it will reply with a Bind
Offer message. Upon seeing the Bind Offer from the
E528/E529, the K595 will bind itself to the advertised
Room ID and RF Settings.
If binding is successful, the K594 will
Flash its LED 3 times
o
Send the thermostat a message to sound its buzzer
o
Reset itself
o
Send a device startup message that includes the K595
o
software version and its battery status.
K595 I/O Maps
I/O Map
Description
0
Entry Door
1
Entry Door Inverted
2
Window
3
Window Inverted
4
Mini Bar
5
Mini Bar Inverted
6
Safe Inverted
7
Safe
8
Common Door
9
Common Door Inverted
10
Connecting Door
11
Connecting Door Inverted
12
Window Segment 0
13
Window Segment 0 Inverted
14
Window Segment 1
15
Window Segment 1 Inverted
16
Window Segment 2
17
Window Segment 2 Inverted
18
Window Segment 3
19
Window Segment 3 Inverted
20
Window Segment 4
PN 292-103
Default Address
209
209
210
210
219
219
219
219
219
219
219
219
211
211
212
212
213
213
214
214
215