In manual functioning, the MITOS VT6 AIR allows to control run-stop and/or change the frequency of inverter
functioning, to a fix value which can be set through the parameter manual Set point.
To enable the manual functioning the following points are necessary:
Modality = CONTROL
Control type = MANUAL
It is possible to set the Modality only by the programming menu.
If the Modality parameter is set to COMMAND, the setting of the parameter command Type is possible through the
programming menu and through the normal functioning menu, pressing for at least 3 seconds the button MAN/AUTO.
The continuous pressure MAN/AUT allows to change the value from AUTOMATIC to MANUAL, and vice versa.
Pressing the button MAN/AUTO for less then 3 seconds, you can only see the type of functioning selected at the
moment.
The possibility to control just the run-stop, just the frequency or both, depends on the CMOD and FMOD values of
Inverter, as shown in the appendix (
If the MITOS VT6 AIR has the frequency control (
first line of the display. Otherwise, in case of lack of frequency control, in the first line of the display you will
see the information selected through the parameter Variable Monitor 1.
In the second line
Variable Monitor 2. However, through the keys UP and DOWN, it is easy to reach all the other information available.
The value Manual Set point can be changed through the parameters programming menu and through the normal
functioning mode. In this last case, if the Set point Storing is set on YES, the change of the set point is automatically
stored and it will be kept even when the card is off; otherwise, if this parameter is set on NO, the change of the set-point
won't be stored. The change of the Manual Set Point from normal functioning menu is performed as follows:
1. with keys UP and DOWN, program "Set" in the second line of the display
2. press the button MON (the second like will flash)
3. change the value through UP and DOWN
4. press the button MON (the second line will stop flashing and the value will be stored)
If the MITOS VT6 AIR has the run-stop control, (
the inverter will stop. When the inverter is in start and the engine is in spin, in the first line of the display, on the right
side, it appears a symbol to indicate the rotation way.
In the manual functioning, ACC and DEC Inverter parameters are automatically set equal to the values of ACC manual/
DEC manual parameters.
02/10/2015

FUNCTIONING "MANUAL"

1
).
of the display, after the card start, you can find the information selected through the parameter
1
), you will see the real frequency reference value in the
1
), pressing START the inverter will start work; pressing STOP/RESET
8 / 17
Manual_MITOS_VT6_AIR_ver3p3_eng