Functioning Parameters - Toshiba MITOS VT6 AIR User Manual

Table of Contents

Advertisement

The parameters programming menu is accessible in the normal functioning menu, by pushing MON button for at least 3
seconds. After the 3 seconds, it is necessary to insert a password. With UP and DOWN, you can change the number
referred to the password, between 0 and 999. Once set the correct value, press MON to confirm. Each wrong password
value allows to view just a part of the available parameters, the first eight in the following pattern. In the programming
menu, you can select the parameter with the buttons UP and DOWN. Then, when the parameter is selected, the
parameter will flash pressing the button MON. Value can be changed through buttons UP and DOWN. To store the new
value, you need to press again MON (the parameter stops flashing). To quit the programming menu, just press
MAN/AUTO.
Here follow all the functioning parameters of MITOS VT6 AIR.
PARAMETER
Hysteresis
Constant PID Kp
Constant PID Ki
Constant PID Kd
ACC manual
DEC manual
ACC automatic
DEC automatic
Mode
Rotation sense
Feedback
Pressure unit
Flow unit
Velocity unit
PID Set point
02/10/2015

FUNCTIONING PARAMETERS

FUNCTION
If the PID control is enabled, this act only if:
V > Set point PID + Hysteresis
or
V < Set point PID - Hysteresis
where V is the value measured by the controlled
variable
PID control proportional constant
PID control integrative constant
PID control derivative constant
Value of the ACC parameter sent to the inverter
when Type command = MANUAL.
Value of the DEC parameter sent to the inverter
when Type command = MANUAL.
Value of the ACC parameter sent to the inverter
when Type command = AUTOMATIC.
Value of the DEC parameter sent to the inverter
when Type command = AUTOMATIC.
MITOS VT6 AIR can be used as a simple
display, but it can also send run and/or frequency
variation commends to the Inverter
Sense of engine rotation
Type of variable where the control PID is
performed
Pressure Unit of measurement
Flow Unit of measurement
Velocity Unit of measurement
Set the set-point of the variable where the PID
control is performed
0.0 ÷ 300.0
0.0 ÷ 300.0
0.0 ÷ 300.0
0.1 ÷ 320.0 sec.
0.1 ÷ 320.0 sec.
0.1 ÷ 320.0 sec.
0.1 ÷ 320.0 sec.
4 / 17
POSSIBLE VALUES
2
min = 0; max (
) appendix
- COMMAND
- VISUALIZATOR
- AHEAD
- BACK
- PRESSURE
- VELOCITY
- FLOW
- mmH
O
2
- Pa
- kPa
- mBar
3
- m
/ h (value per 100)
3
- m
/ s
- l / s
m / s
2
min = 0; max (
) appendix
Manual_MITOS_VT6_AIR_ver3p3_eng