User Guide | Superheat controller, EKC 315A
Define input signal on the analog input AIA:
0: no signal,
1: Temperature setpoint. 0-20 mA
2: Temperature setpoint. 4-20 mA
3: Displacement of superheat reference. 0-20 mA
4: Displacement of superheat reference. 4-20 mA
Set supply voltage frequency
Select display for "normal picture"
(Display the item indicated in parenthesis by
briefly pressing the bottom button)
1: Superheat (Temperature)
2: Valve's opening degree (Superheat)
3: Air temperature (Temperature reference)
Manual control of outputs:
OFF: no manual control
1: Relay for solenoid valve: select ON
2: AKV/A output: select ON
3: Alarm relay activated (cut out)
Working range for pressure transmitter – min.
value
Working range for pressure transmitter – max.
value
(Setting for the function o09, only AKV and TQ)
Set the temperature value or opening degree
where the output signal must be minimum (0 or
4 mA)
(Setting for the function o09, only AKV and TQ)
Set the temperature value or opening degree
where the output signal must be maximum (20
mA)
Refrigerant setting
1=R12. 2=R22. 3=R134a. 4=R502. 5=R717. 6=R13.
7=R13b1. 8=R23. 9=R500. 10=R503. 11=R114.
12=R142b. 13=User defined. 14=R32. 15=R227. 16=R401A.
17=R507. 18=R402A. 19=R404A. 20=R407C. 21=R407A.
22=R407B. 23=R410A. 24=R170. 25=R290. 26=R600.
27=R600a. 28=R744. 29=R1270. 30=R417A. 31=R422A.
32=R413A. 33=R422D. 34=R427A. 35=R438A
Service
TQ valve's actuator temperature
Reference of the valve's actuator temperature
Analog input AIA (18-19)
Analog output AO (2-5)
Read status of input DI
Thermostat cut-in time
Temperature at S2 sensor
Superheat
Superheat reference
Read AKV valve's opening degree
Read evaporating pressure
Read evaporating temperature
Temperature at S3 sensor
Temperature reference
Read signal at pressure transmitter input
*) This setting will only be possible if a data communication module has been
installed in the controller.
Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep both buttons depressed at the same time as you recon nect the supply voltage
© Danfoss | DCS (ADAP-KOOL®) | 2015-03
o10
0
4
0
o12
50 Hz
60 Hz
0
o17
1
3
1
o18
off
3
Off
o20
-1 bar 60 bar -1.0
o21
-1 bar 60 bar 12
o27
-70°C
160°C
-35
o28
-70°C
160°C
15
o30
0
35
0
u04
°C
u05
°C
u06
mA
u08
mA
u10
on/off
u18
min.
u20
°C
u21
K
u22
K
u24
%
u25
bar
u26
°C
u27
°C
u28
°C
u29
mA
The controller can give the following messages:
E1
Fault in controller
E11
Valve's actuator temperature outside its range
E15
Cut-out S2 sensor
E16
Shortcircuited S2 sensor
Error message
E17
Cut-out S3 sensor
E18
Shortcircuited S3 sensor
The input signal on terminals 18-19 is outside
E19
the range.
The input signal on terminals 14-15 is outside
E20
the range (P0 signal)
A1
High-temperature alarm
Alarm message
A2
Low-temperature alarm
A11
No refrigerant has been selected
DKRCI.PS.RP0.D2.02 | 520H7653| 9