r the air conditioner, connect a power wire with the
following specifications.
Model RAV-
GM110, GM140
380-415V 3N~, 50Hz
Power supply
380V 3N~, 60Hz
Maximum running current
14.10 A
Installation fuse rating
20 A (all types can be used)
H07 RN- or 60245 EC 66
Power supply wire
2
(5 x 2.5 mm
H07 RN- or 60245 EC 66
System interconnection
wires
(4 x 1.5 mm
2
How to wire
1. Remove the mounting screws (2 pieces), open the
electrical control box cover.
2. Connect the power supply wires and system
interconnection wires to the terminal block of the
electrical control box.
3. Tighten the screws of the terminal block, connect
the wires matching the terminal numbers (Do not
apply tension to the connecting section of the
terminal block.)
4. Close the electrical control box cover, attach the
mounting screws.
to the outdoor unit terminal, prevent water from
coming into the outdoor unit.
electrical insulation tape. Process them so that
they do not touch any electrical or metal parts.
wire joined to another on the way.
Use wires long enough to cover the entire length.
Power supply
terminal block
terminal block
Earth screw
Earth screw
Pipe valve
fixing plate
System
Power supply wire
interconnection
wire
33-EN
Stripping length power cord and
connecting wire
or more)
Connecting line
Earth wire
or more)
Wiring diagram
*
or details on the remote controller wiring /
installation, refer to the nstallation Manual enclosed
with the remote controller.

Single system

Remote controller
Remote controller wiring
A
B
r side
1
2
3
System interconnection
wires
1
2
3
Outdoor side
L1(R)
L2(Y)
L3(B)
Power supply
Simultaneous twin system
Remote controller
Remote controller
wiring
A
B
r side
1
2
3
System
interconnection wires
1
2
3
Outdoor side
N
L1(R)
L2(Y)
L3(B)
Power supply
* Use 2-core shield wire (MVVS 0.5 to 2.0 mm² or
more) for the remote controller wiring in the
simultaneous twin system to prevent noise
problems. Be sure to connect both ends of the shield
wire to earth leads.
* Connect earth wires for each indoor unit in the
simultaneous twin system.
– 17 –
8

Earthing

WARNING
Be sure to connect the earth wire. (grounding work)
Incomplete grounding may cause an electric shock.
Connect the earth wire properly following applicable technical standards.
Connecting the earth wire is essential to preventing electric shock and to reducing noise and electrical charges on
Earth wire
the outdoor unit surface due to the high-frequency wave generated by the frequency converter (inverter) in the
Power supply
outdoor unit.
If you touch the charged outdoor unit without an earth wire, you may experience an electric shock.
9

Finishing

After the refrigerant pipe, inter-unit wires, and drain pipe have been connected, cover them with finishing tape and
clamp them to the wall with off-the-shelf support brackets or their equivalent.
Keep the power wires and system interconnection wires off the valve on the gas side or pipes that have no heat
insulator.
10

Test run

• Turn on the leakage breaker at least 12 hours before starting a test run to protect the compressor during
N
startup.
To protect the compressor, power is supplied from the 380-415 VAC input to the unit to preheat the compressor.
• Check the following before starting a test run:
• That all pipes are connected securely without leaks.
• That the valve is open.
Remote
If the compressor is operated with the valve closed, the outdoor unit will become overpressurized, which may
controller
inter-unit
damage the compressor or other components.
wiring
If there is a leak at a connection, air can be sucked in and the internal pressure further increases, which may
cause a burst or injury.
• Operate the air conditioner in the correct procedure as specified in the Owner's Manual.
A
B
oor
side
1
2
3
11

Annual maintenance

ndoor
power
inter-unit
For an air conditioning system that is operated on a regular basis, cleaning and maintenance of the indoor / outdoor
wiring
units are strongly recommended.
As a general rule, if an indoor unit is operated for about 8 hours daily, the indoor / outdoor units will need to be
cleaned at least once every 3 months. This cleaning and maintenance should be carried out by a qualified service
person.
Failure to clean the indoor / outdoor units regularly will result in poor performance, icing, water leaking and even
compressor failure.
34-EN