Diginet RAPIX eHub Installation Manual

Lighting control system

Advertisement

Quick Links

JOSEPH JOUKHADAR
sels@automated.net.au
+61 2 9247 0731
Suite 4, Level 5
37 Pitt Street
Sydney NSW 2000
Installation Guide
RAPIX Lighting Control System - eHub
DGOZ-EHUB-4G-2S
Designed in Australia to
meet Australian Standards
and installation conditions
DIGINET.NET.AU

Advertisement

Table of Contents
loading

Summary of Contents for Diginet RAPIX eHub

  • Page 1 JOSEPH JOUKHADAR sels@automated.net.au +61 2 9247 0731 Suite 4, Level 5 37 Pitt Street Sydney NSW 2000 Installation Guide DGOZ-EHUB-4G-2S RAPIX Lighting Control System - eHub Designed in Australia to meet Australian Standards and installation conditions DIGINET.NET.AU...
  • Page 2: Product Package Contents

    DALI Lines. If you require information or assistance regarding the installation, configuration, or operation of the eHub, contact Technical Services at Diginet Control Systems. Contact details are provided on the back cover of this guide and also at...
  • Page 3: Product Features

    The eHub is a compact unit which fits through a standard 90mm downlight ceiling hole and is suitable for locating in a ceiling void. The eHub is configured via the Diginet RAPIX software suite. 5. Product features •...
  • Page 4 RAPIX Lighting Control System RAPIX Lighting Control System - eHub 7. Inputs and output connections The eHub connects to the following: • 12V dc SELV power supply connection • A DALI Line, with up to 64 DALI devices (each with a DALI Short Address) connected to the line •...
  • Page 5: Connections Overview

    RAPIX Lighting Control System RAPIX Lighting Control System - eHub 9. Powering connected input peripherals The eHub supplies power to all connected input peripherals such as RAPIX modular switches and 12V dc sensors. 10. Connections Overview WARNING - DALI Lines must be considered at 240Vac electrical mains potential due to basic equipment isolation and cable segregation between mains and DALI.
  • Page 6 Each DALI Line requires an external DALI compliant power supply to be connected before it will operate. A Diginet DALI Power Supply, item number DGLMPS01 (purchased separately), can be connected to each DALI Line to fulfil this requirement.
  • Page 7 Toggle between off and the current Level • Issue a scene All commissioning is carried on via Diginet RAPIX software suite. The configuration is downloaded to the eHub via a DALI line. Do not connect RAPIX modular switches to the building/house ac mains supply.
  • Page 8 RAPIX Lighting Control System - eHub 13.2. Range The following RAPIX modular switches can be connected to each of the four smart input peripheral connectors on the eHub. Diginet Part Number Description DGOZ-MOSW-M-PB RAPIX modular switch – Push Button Master DGOZ-MOSW-M-RO RAPIX modular switch –...
  • Page 9 RAPIX Lighting Control System RAPIX Lighting Control System - eHub 14.1. RAPIX modular switch eHub patch lead connections Connection between a master RAPIX modular Connection between the eHub and RJ-45 patch lead switch and RJ-45 patch lead 14.2. Connections from the eHub to a master RAPIX modular switch The diagram below shows the connections between the eHub and a master RAPIX modular switch.
  • Page 10 RAPIX Lighting Control System RAPIX Lighting Control System - eHub 15. Connecting masters to slaves Slave RAPIX modular switches connect directly to masters. Slaves have an integrated flying lead with a male connector. Masters have matching female sockets. Connection between a master and slave RAPIX modular switch 15.1.
  • Page 11 The following occupancy sensors can be connected and powered from one of the two eHub sensor inputs. Manufacture Item Number Description Gerard Lighting Diginet DGEMS360CL Smart Scan PIR Sensor, 360 degree ceiling mount, recessed Sensor Switch CM-PDT-9-AU Sensor Switch dual technology sensor with PIR and Microphonics detection, ceiling mounted A sensor patch lead is provided with the above sensors and connected to the eHub as shown below.
  • Page 12 19. Commissioning and testing Commissioning of the eHub, which forms part of a complete RAPIX Lighting Control System, should be carried out using the Diginet RAPIX software suite, which can be downloaded from the Diginet web site at diginet.net.au. 20. Resetting the eHub Pressing and holding the recessed reset button (with a paperclip or similar) for 45 seconds will perform a complete factory reset and all settings in the eHub will be lost.
  • Page 13 RAPIX Lighting Control System RAPIX Lighting Control System - eHub 24. eHub dimensions 25. eHub standards and compliance eHub is designed to meet/exceed the following Australian and International standards. Australian/New Zealand EMC and Electrical Safety Frameworks and Standards. Regulation Standard Title AS/NZS CISPR 22:2009 Information Technology Equipment –...
  • Page 14 RAPIX Lighting Control System RAPIX Lighting Control System - eHub 26. RAPIX modular switch range specifications Parameter Specification Available types Push Button Master Push Button Slave Rocker Master Rocker Slave Rotary Master Rotary Slave LED colours Master and slave RAPIX modular switches include both white and amber LED indicators.
  • Page 15: Product Warranty

    7.1.3. fax to 1300 95 3257; or 7.1.4. email to sales@diginet.net.au. 7.2. return the Goods at the Owners expense to the return address notified by Gerard Lighting together with all accessories, instructions, specifications or other material supplied with the Goods and a notice in writing: 7.2.1.
  • Page 16 Padstow NSW 2211 Contact General Enquiries: 1300 95 DALI (3254) or sales@diginet.net.au Technical Services: 1300 95 3244 or support@diginet.net.au Fax: 1300 95 3257 Diginet is a brand of the Gerard Lighting Group Version Issue 1 - September 2015 Item 14-12-008-001-01...