Installing The Programmer; Removing The Programmer; Mounting The Programmer On The Subbase - Honeywell R4140G Installation Instructions Manual

Flame safeguard programming controls
Table of Contents

Advertisement

R4140G, L AND M FLAME SAFEGUARD PROGRAMMING CONTROLS
Test
R4140
Test
No.
Models
Jumpers Voltmeter
13
All R4140L
L18 and
modeIs
14-11
14
All R4140L
L1-15
models
and
14-11
15
All R4140G
12-11
and R4140L
models
16
R4140M
L1-10
models with
open damper
contacts
17
R4140M
L1-8
models with
open damper
contacts
Final
All models
Installing the Programmer (Fig. 3)
Open the master switch.
Make sure no subbase wiring is projecting out beyond
the terminal blocks. Tuck in wiring against the back of
the subbase so it does not interfere with the contacts.
Grasp the handle of the programmer chassis and
engage the chassis hinge brackets with the pivot pins
at the bottom of the subbase.
Swing the chassis inward until the spring connectors
engage the knife-blade contacts. Push in until the
contacts are fully engaged.
Tighten the chassis retaining screw securely.

Removing the Programmer

Open the master switch.
Loosen the chassis retaining screw.
Pull outward on the handle.
Disengage the chassis hinge brackets from the
subbase pivot pins.
60-0770—2
Table 2. Static Tests of External Devices (Continued).
Normal
Operation
13-L2
Firing rate motor drives closed;
line voltage at terminal 13 after
motor closes.
13-L2
Firing rate motor drives closed;
line voltage at terminal 13 after
motor closes.
1. Raise setpoint of Series 90
Controller—firing rate motor
should drive toward open.
2. Lower setpoint of Series 90
Controller—firing rate motor
should drive toward closed.
If damper control is used,
actuator drives damper open.
13-L2
If damper control is used,
spring return drives actuator
and damper closed; line
voltage at terminal 13 after
actuator closes.
CAUTION
After completing these tests, open the master switch and remove all test jumpers from the
subbase terminals. Also remove bypass jumpers from the low fuel pressure limits (if used).
If Operation is Abnormal,
Check the Items Listed Below
1. Low Fire switch is connected between
terminals 8 and 13. If not, proceed to test
no. 14.
2. Low Fire switch is closed.
3. Firing rate motor and transformer are OK.
1. Low Fire switch is connected between
terminals 15 and 13. If not, proceed to test
no. 15.
2. Low Fire switch is closed.
3. Firing rate motor and transformer are OK.
1. Series 90 Controller is OK.
2. Firing rate motor and transformer are OK.
1. Jumper wire is installed between
terminals 11 and 12.
2. Damper actuator is OK.
1. Low Fire switch is closed.
2. Damper actuator is OK.
KNIFE-BLADE
CONTACTS (20)
WIRING
SUBBASE
PIVOT PIN (2)
Fig. 3. Mounting the programmer on the subbase.
6
SPRING
CONNECTORS
CHASSIS
RETAINING
SCREW
HANDLE
PROGRAMMER
CHASSIS
HINGE
M7965
BRACKET (2)