Troubleshooting

See Table 3 below for symptoms and remedies.
Table 3: Symptoms and Remedies
Symptom
Note:
LCD Display is blank
after the 2 minute
warmup period (8002
and 8008 models)
1. Remove the sensor from the wiring
2. Ensure that the sensor pins that connect
3. If the LCD display is still blank after
Green light is not
1. Remove the sensor from the wiring
illuminated (8001
and 8008 models)
after the two minute
warmup period.
2. Ensure that the two pins on the sensor
3. If the green light is still not illuminated
4. If there is no output signal, call GE
Page 6
Remedy
Follow the Remedy Steps in
numerical order.
plate and check the voltage on pins 1
and 2 of the 2-pin terminal block. The
voltage should be: 18-30 VAC RMS or
18 - 42 VDC
to the 2-pin terminal block are not
broken, bent, or damaged.
replacing the sensor on the mounting
plate, call GE Telaire or your
distributor/dealer for a return
authorization number.
plate and check the voltage on pins 1
and 2 of the 2-pin terminal block. The
voltage should be: 18-30 VAC RMS or
18 - 42 VDC.
that connect to the 2-pin terminal block
are not broken, bent, or damaged.
after replacing the sensor on the
mounting plate, try verifying the sensor
operation using the UIP 8000 computer
interface or checking the output signal
on the building automation system.
Telaire or your distributor/dealer for a
return authorization number
.
Table 3: Symptoms and Remedies (cont.)
Symptom
1. Compare the sensor reading to a GE
Suspect the sensor is
Telaire 7001 hand-held CO
out of calibration.
2. Take another sensor from the building
and replace the suspect sensor to see if
the readings are similar.
3. Connect the sensor outdoors (if
possible). The readings should be
between 350 and 450 ppm.
4. Connect the sensor to nitrogen gas from
a Model 2075 calibration kit. The
reading should be close to zero.
5. If the sensor still proves to be out of
calibration, calibrate the sensor
according to the instructions included in
your calibration kit, or call for a Return
Authorization (RA) number before
returning the sensor to GE Telaire for
factory calibration.
Relay does not
1. Using the LCD menu or the UIP 8000
actuate at the proper
computer interface, verify that the relay
setpoint.
setpoint is correct.
2. Return the sensor to normal operating
mode, and breathe into the sensor to
raise the ppm value above the relay
setpoint.
3. If the relay does not actuate at the
proper setpoint, call GE Telaire or your
distributor/dealer for a Return
Authorization (RA) number.
Remedy
monitor.
2
Telaire Ventostat™ 8000 Series