Download Print this page

Contact Information - Philips ActiLume Classic Installation And Programming Manual

Advertisement

Function Definitions
2 Occupancy Time Delay
The length of time an occupancy sensor will
keep the lights on and at full bright after it last
detects occupancy (assuming minimum on
time has been met)
4 100 Hour Burn-In / Test Mode
Disables Minimum On Time, sets Occupancy
Time Delay to 30 sec, and shortens all
photocell transition and dimming rates. Mode
will expire after 10 min or if function 4 is set
back to Normal.
100 Hour Burn-In
Overrides relay on and/or dimming output
to full bright (typically for lamp seasoning)
Test Mode
Disables Minimum On Time and sets
Occupancy Time Delay to 30 sec. Mode
will expire after 10 min or if function 4 is
set back to Normal.
Programming
Please read all 3 steps before programming
1. Enter a programming function by pressing
button, on front of device, the number of
times as the desired function number from
the tables below (e.g., press twice for
function 2, occupancy time delay).
2. LED will flash back the selected function's
current setting (e.g., 5 flashes for 10 minute
time delay). To change setting, proceed to
step 3 before flash back sequence repeats 3
times. To exit the current function or to
change to a different function, wait for
sequence to repeat 3 times then return to
step 1.
3. Press button the number of times
indicated in the particular function's detailed
table for the NEW desired setting (e.g., press
3 times for 5 min). As confirmation of setting
change, LED flashes back the NEW setting 3
times before exiting.
2 Occupancy Time Delay
Selection
Time
1
30 sec
2
2.5 min
3
5 min
4
7.5 min
5
10 min*
6
12.5 min
7
15 min
8
17.5 min
9
20 min
* default setting
Warranty Statement
The Philips ActiLume products, when properly installed and under normal conditions of use (without overload,
abuse or alteration), is warranted to you, the original user, for a period of two (2) years from the date of original
purchase, to be free from defects in materials and workmanship. If during the warranty period you believe the
purchased product or any part thereof has such a defect, you must return the product (or part) at your cost
during such period, with proof of purchase (or if installed by a third party a written explanation of installation
transaction with proof of date), to Philips Lighting Electronics N.A (1-800-372-3331 / www.philips.com/advance),
for repair or replacement (or to an authorized Philips Lighting Electronics N.A. supplier which agrees in advance to
handle the return and replacement by factory authorization). If the product or part is found by Philips to have
been defective in material or workmanship it will be repaired or replaced (as deemed necessary by Philips Lighting
Electronics N.A.), and the replacement will be returned to you free of charge. The original user is solely
responsible for any costs associated with removal and re-installation of the product and shipping to Philips Lighting
Electronics N.A. or its authorized supplier.
©2011 Philips Lighting Electronics North America.
A Division of Philips Electronics North America Corporation.
All rights reserved.
Printed in the USA
Published 10/1
Part No. LRM2310-INSTALL-B
10 Minimum On Time
The length of time required for lamps to be
on in order to prevent all short cycling that
shortens lamp life. If occupancy time delay
expires prior to minimum on time being
satisfied, the lamps will remain on until time
has been met.
Programming Functons
Function
Description
2
Occupancy Time Delay
4
Test Mode & 100 hr Burn-In
10
Minimum On Time
4 Test Mode / 100 hr Burn-In
Selection
Operation
1
Normal*
2
Run 100 hr Burn-In
6
Test Mode
1
Test Mode will disable Minimum On Time,
1
set Occupancy Time Delay to 30 sec. Mode
will expire after 10 min or if function 4 is set
back to Normal.
* default setting
10 Minimum On Time
Selection
Time
1
0 min
2
15 min*
3
30 min
4
45 min
5
60 min
* default setting

Contact Information

Philips Lighting
10275 West Higgins Road
Rosemont, IL 60018
Customer Care/Technical Service: 800-372-3331
Email: tech.service.rosemont@philips.com
Website: www.philips.com

Advertisement

loading

This manual is also suitable for:

Lrm2315Lrm2310Lrm2320Lrm2325