pass & seymour RW500U Installation Instructions

Pir occupancy sensor switch

Advertisement

Quick Links

340800_RevB_IS_12266
4/23/07
9:55 AM
TEST MODE
To test the detection coverage:
During the TEST mode, the controlled load turns ON for 5 seconds each time the
sensor detects occupancy.
1. Press and hold the ON/OFF button. After 10 seconds the lighted switch turns
OFF. The controlled load turns ON if it was not already ON. The sensor is now
in a TEST mode that lasts 5 minutes. (You can end the TEST mode sooner by
pressing the ON/OFF button for another 10 seconds).
2. Move out of the coverage area or stand very still. The controlled load turns
OFF after 5 seconds if no motion is detected.
3. Move into the coverage area. The controlled load turns ON for 5 seconds each
time the sensor detects motion. After 5 seconds expire without motion
detection, the load turns OFF. The controlled load turns ON automatically with
the next motion detection and stays ON for 5 seconds.
4. Repeat as necessary to ensure that the desired coverage areas are within
detection range.
TROUBLESHOOTING
Load will not turn ON (lighted switch is visible):
• Move in front of the sensor to automatically turn lights ON. If lights do not
turn ON, press the ON/OFF button. The lighted switch should turn OFF and
the controlled load should turn ON, if not:
• Check the light bulb.
• Turn OFF power to the circuit then check wire connections.
• Remember that if the load is turned OFF manually, Automatic-ON is
reenabled only after no motion is detected for 5 minutes.
Light will not turn ON (lighted switch is NOT visible):
• Check the light bulb.
• Make certain that the circuit breaker is ON and functioning.
• Turn OFF power to the circuit then check wire connections.
Visit our website at: www.passandseymour.com
Page 1
Load will not turn OFF:
The time delay is 5 minutes (fixed time delay).
• Make sure no motion occurs in the coverage area until the time delay
expires.
• If the load does not turn OFF, call Technical Support at 800.223.4185.
• Hot air currents and heat radiant devices can cause false detection. Make
sure the sensor is at least 6 feet (2 meters) away from devices that are a
significant heat source (e.g heater, heater vent, high wattage light bulb).
• Press the ON/OFF button. If the controlled load does not turn OFF, turn
OFF the power to the circuit, then check wire connections.
Limited FIVE YEAR Warranty
Pass & Seymour/Legrand will remedy any defect in workmanship or material in Pass & Seymour/Legrand prod-
ucts which may develop under proper and normal use within five years from the date of purchase by a consumer:
(1) by repair or replacement, or, at Pass & Seymour/Legrand's option, (2) by return of an amount equal to the
consumer's purchase price. Such remedy is IN LIEU OF ANY AND ALL EXPRESSED OR IMPLIED WARRANTIES
OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Such remedy by Pass & Seymour/Legrand
does not include or cover cost of labor for removal or reinstallation of the product. ALL OTHER FURTHER ELE-
MENTS OF DAMAGE (INCIDENTAL OR CONSEQUENTIAL DAMAGES) FOR BREACH OF ANY AND ALL EXPRESSED
OR IMPLIED WARRANTIES including warranties OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PUR-
POSE ARE EXCLUDED HEREBY. (Some states do not allow disclaimer or exclusion or limitation of incidental or
consequential damages, so the above disclaimers and limitation or exclusion may not apply to you.) ANY IMPLIED
WARRANTIES INCLUDING WHERE REQUIRED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTIC-
ULAR PURPOSE SHALL BE LIMITED TO THE FIVE YEAR PERIOD SET FORTH ABOVE. (Some states do not allow
limitation on how long an implied warranty lasts, so the above limitation may not apply to you.)
To ensure safety, all repairs to Pass & Seymour/Legrand products must be made by Pass & Seymour/Legrand
or under its specific direction. Procedure to obtain performance of any warranty obligation is as follows:
(1) Contact Pass & Seymour/Legrand, P.O. Box 4822, Syracuse, NY 13221 for instructions concerning return
or repair; (2) return the product to Pass & Seymour/Legrand, postage paid, with your name and address and a
written description of the installation or use of the Pass & Seymour/Legrand product, and the observed defects
or failure to operate, or other claimed basis for dissatisfaction.
This warranty gives you specific legal rights and you may also have other rights which vary from state to state.
Technical Support: 800.223.4185 • www.passandseymour.com
P.O. Box 4822, Syracuse, NY 13221-4822
340800 Rev. B 08129
Please read all instructions before installing
RW500U
PIR Occupancy Sensor Switch
with Manual
ON/OFF
Lens
Lighted Switch
ON/OFF Button
SPECIFICATIONS
Voltage
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120VAC, 60Hz
Load (Single Pole Circuit)
Incandescent . . . . . . . . . . . . . . . . . . . . . . . . . . 25-500 Watts
Time Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 minutes
Environment . . . . . . . . . . . . . . . . .Residential Indoor use only
Operating Temperature . . . . . . . .32° to 131°F (0° to 55°C)
Humidity . . . . . . . . . . . . . . . . . . . .95% RH, non-condensing
Electrical Supply Wire . . .minimum temp rating 167°F (75°C)
Tools Needed:
Insulated Screwdriver
Wire Strippers
Syracuse, NY 13221

Advertisement

loading

Summary of Contents for pass & seymour RW500U

  • Page 1 Page 1 Please read all instructions before installing TEST MODE Load will not turn OFF: RW500U The time delay is 5 minutes (fixed time delay). To test the detection coverage: PIR Occupancy Sensor Switch • Make sure no motion occurs in the coverage area until the time delay During the TEST mode, the controlled load turns ON for 5 seconds each time the expires.
  • Page 2 • Connect the green or non- To help you locate the RW500U in a dark room, a green LED illuminates the RW500U, replacing lamps, or doing any electrical work.
  • Page 3 All information in this drawing is the property of P&S/Legrand and cannot be copied or used without the written approval of P&S/Legrand. Drawn by ROUGEAU SYRACUSE, NEW YORK MarCom Engineering Title: RW500U Installation Instructions Orig. Drawing Date: 28 FEB 06 Drawing #: Rev. #: TITLE BOX PG Scale: 1:1 08129 Revision Date:...