Quick Links

SENSOR ADJUSTMENT
DO NOT OVERTURN TRIMPOTS WHEN ADJUSTING THE SENSOR!
1. To test unit operation, press the ON/OFF button to turn the load on.
2. Remove the button cover to access the adjustment controls. Use a small,
flat blade screwdriver to press down the locking tab at the top of the button,
then gently pry it off.
a) Set the time delay to the "walk test" position (fully counterclockwise).
b) Leave the room. The load should go off after 30 seconds.
3. To test sensitivity:
a) Make no motion for 3 seconds.
b) Wave your hand sideways in front of the sensor at a distance of
approximately 12". The LED blinks when movement is detected.
Typically, the sensitivity should be at maximum (fully clockwise).
4. Set the light level when the controlled light would normally be turned off
due to the presence of sufficient daylight or other electric light. [If this
feature is not needed, leave the light level at maximum (fully clockwise)].
a) Set the Time Delay to at least 5 minutes. This takes the sensor out of
Walk-test mode, and enables the light level feature.
b) Set the Light level to 50% (12 o'clock position) which is approximately
100fc. Let the sensor time out so lights are off. Enter the space and
lights should remain off.
c) Make sure your body does not cast a shadow on the sensor, and adjust
the light level trimpot clockwise in small increments.
d) After each adjustment, wait 5-10 seconds to see if the lights turn on.
Repeat until the lights turn on. At this setting the load connected to the
sensor will not turn on if light levels are above the current illumination.
Note: Users can override this function by placing their hand in front of the
sensor to block incoming light. The load will then remain on until the
space is unoccupied or the light level rises above the setpoint and the
time delay expires.
Time Delay (T)
5. Reset the time delay to the
Shown as set for
15 minutes
desired setting. The time delay
10 minutes
20 minutes
can be set from 30 seconds
5 minutes
(see Walk-test feature, light
25 minutes
level feature is disabled)
to 30 minutes in 5-minute
30 seconds
30 minutes
S
L
T
increments.
(Walk-test)
Visit our website: www.legrand.us
TROUBLESHOOTING
Load will not turn on:
• LED does not flash:
- I f the sensor fails to operate after the initial warm-up period, use a small
flat blade screwdriver to pry off button and slide the line power reversing
switch to the opposite position. This will re-initiate the warm-up period.
- Check the sensitivity for proper configuration.
- Check all wire connections. Verify the ground wire is tightly secured.
• LED does flash:
- P ress the ON/OFF button. If load does not turn on, check all wire
connections and verify the load wire is tightly secured.
- C heck the light level trimpot. Turn it fully clockwise
• If load still does not turn on, call 800.223.4185 for technical support.
Load will not turn off:
• T he time delay can be set for 30 seconds
(Walk Test), 5, 10, 15, 20, 25, or 30
minutes. Ensure that the time delay is
set to the desired delay and that there is
no movement within the sensor's view
for that time period.
• T o quickly test the unit for proper
operation, turn the time delay to
minimum (fully counterclockwise) and
move out of the sensor's view. Load
should turn off after
30 seconds.
• If load still does not turn off, call
800.223.4185 for technical support.
Sensing motion outside desired area:
• O paque adhesive tape is included with the sensor and can be used to limit the
detection areas. See Masking the Lens.
• Adjust sensitivity counterclockwise to reduce excessive sensitivity.
Call 800.223.4185 for Technical Support
WARRANTY INFORMATION
Pass & Seymour/Legrand warranties its products to be free of defects
in materials and workmanship for a period of five (5) years. There are
no obligations or liabilities on the part of Pass & Seymour/Legrand for
consequential damages arising out of, or in connection with, the use or
performance of this product or other indirect damages with respect to loss of
property, revenue or profit, or cost of removal, installation or reinstallation.
Please
Recycle
P.O. Box 4822, Syracuse, NY 13221-4822
Technical Support: 800.223.4185
www.legrand.us
340914
PTWSP‑250
PlugTail
Passive Infrared Wall Switch
Occupancy Sensor
SPECIFICATIONS
PTWSP-250 Voltages ............................................120 or 277VAC, 60Hz
Load Requirements
@ 120VAC, 60Hz ............. 0-800W ballast & tungsten, 1/6 hp
@ 277VAC, 60Hz ........................................... 0-1200W ballast
Time Delay Adjustment ...................................30 seconds - 30 minutes
Sensitivity Adjustment . ..........................................Minimum-Maximum
Light Level Adjustment ..................................................... 10 - 200 + FC

Advertisement

loading

Summary of Contents for pass & seymour PTWSP-250

  • Page 1 • T he time delay can be set for 30 seconds 4. Set the light level when the controlled light would normally be turned off (Walk Test), 5, 10, 15, 20, 25, or 30 due to the presence of sufficient daylight or other electric light. [If this minutes. Ensure that the time delay is feature is not needed, leave the light level at maximum (fully clockwise)]. set to the desired delay and that there is no movement within the sensor’s view a) Set the Time Delay to at least 5 minutes. This takes the sensor out of SPECIFICATIONS for that time period. Walk-test mode, and enables the light level feature. • T o quickly test the unit for proper b) Set the Light level to 50% (12 o’clock position) which is approximately PTWSP-250 Voltages ..........120 or 277VAC, 60Hz operation, turn the time delay to 100fc. Let the sensor time out so lights are off. Enter the space and Load Requirements minimum (fully counterclockwise) and lights should remain off. @ 120VAC, 60Hz ..... 0-800W ballast & tungsten, 1/6 hp move out of the sensor’s view. Load c) Make sure your body does not cast a shadow on the sensor, and adjust should turn off after @ 277VAC, 60Hz ........... 0-1200W ballast the light level trimpot clockwise in small increments.
  • Page 2 Top View lower than the set level, the sensor automatically turns on the load. Walk‑test feature: (4.6m) When the Time Delay trimpot is in the fully 4.0' counterclockwise position, (1.2m) the sensor has a 30 second floor time delay and the Light Side View Level function is disabled. 2. Snap connector into PTWSP-250 device as shown. (10.7m) This allows you to quickly 3. Verify connector security and engagement. check the sensor coverage 4. Attach the sensor to the wall by mounting it in the wall box with the two area. mounting screws provided. Masking the lens Override function: 5. Turn on power at the circuit breaker. Opaque adhesive tape is supplied so that In the event of unit failure sections of the sensor’s view can be masked. There is an initial warm‑up period after installation. It may take up to a...
  • Page 3 DESCRIPTION INT: REV. DATE APPROVED 1 PTWSP-250 InstSheet 17 Jan 11 TITLE BOX PAGE ONLY. DO NOT MAKE FILM • DO NOT PRINT MATERIAL: White 80g/m sq Uncoated, prefer recycled stock INK: Black PRINT: 2 sided FLAT (cut) SIZE: 16"W x 6" H FOLDED SIZE: 4"W x 6" H All information in this drawing is the property of Pass & Seymour/ Legrand and cannot be copied or used without the written approval of Pass & Seymour/Legrand. DRAWN BY Loughlin SYRACUSE, NEW YORK...