Noise - Mitsubishi Electric PUHZ-SP125VKA Service Manual

R410a, outdoor unit
Hide thumbs Also See for PUHZ-SP125VKA:
Table of Contents

Advertisement

<Display function of inspection for outdoor unit>
The blinking patterns of both LED1 (green) and LED2 (red) indicate the types of abnormality when it occurs. Types of
abnormality can be indicated in details by connecting an optional part 'A-Control Service Tool (PAC-SK52ST)' to connector
CNM on outdoor controller board.
[Display]
(1)Normal condition
Unit condition
When the power is turned on
When unit stops
When compressor is warming up
When unit operates
(2)Abnormal condition
Indication
Outdoor controller board
LED1 (Green) LED2 (Red)
1 blinking 2 blinking
Connector (63H) is open.
Miswiring of indoor/outdoor unit conne-
2 blinking 1 blinking
cting wire, excessive number of indoor
units (4 units or more)
Miswiring of indoor/outdoor unit co-
nnecting wire (converse wiring or di-
sconnection)
Startup time over
Indoor/outdoor unit communication error
2 blinking
(signal receiving error) is detected by in-
door unit.
Indoor/outdoor unit communication error
(transmitting error) is detected by indoor
unit.
Indoor/outdoor unit communication error
(signal receiving error) is detected by
outdoor unit.
Indoor/outdoor unit communication error
(transmitting error) is detected by outdoor
unit.
3 blinking
Remote controller signal receiving
error is detected by remote controller.
Remote controller transmitting error
is detected by remote controller.
Remote controller signal receiving
error is detected by indoor unit.
Remote controller transmitting error
is detected by indoor unit.
4 blinking
Check code is not defined.
5 blinking
Serial communication error
<Communication between outdoor
controller board and outdoor power
board>
<Communication between outdoor
controller board and M-NET P.C. board>
Communication error of M-NET
system
*Check code displayed on the remote controller.
OCH671
Outdoor controller board
LED1 (Green)
LED2 (Red)
Lighted
Lighted
Lighted
Not lighted
Lighted
Not lighted
Lighted
Lighted
Check
Contents
code*
1Check if connector (63H) on the outdoor controller board is
F5
2Check continuity of pressure switch (63H) by tester.
1Check if indoor/outdoor connecting wire is connected correctly.
2Check if 4 or more indoor units are connected to outdoor unit.
3Check if noise entered into indoor/outdoor connecting wire
4Re-check error by turning off power, and on again.
E6
1Check if indoor/outdoor connecting wire is connected correctly.
2Check if noise entered into indoor/outdoor connecting wire or
E7
3Check if noise entered into indoor/outdoor controller board.
4Re-check error by turning off power, and on again.
E0
1Check if connecting wire of indoor unit or remote controller
2Check if noise entered into transmission wire of remote
E3
3Re-check error by turning off power, and on again.
E4
E5
1Check if remote controller is MA remote controller(PAR-21MAA).
EF
2Check if noise entered into transmission wire of remote controller.
3Check if noise entered into indoor/outdoor connecting wire.
4Re-check error by turning off power, and on again.
1Check refrigerant pipes for disconnection or leakage.
PL
2After the recovery of refrigerant, vacuum dry the whole
3Refer to section "9-6 HOW TO CHECK THE PARTS".
4Check refrigerant circuit for operation.
1Check if connector (CN4) on outdoor controller board and
Ed
2Check if there is poor connection of connector on outdoor
3Check M-NET communication signal.
A0~A8
67
Check code
00, etc.
08, etc.
C5, etc.
Error
Inspection method
not disconnected.
or power supply.
power supply.
is connected correctly.
controller.
refrigerant circuit.
outdoor power board is not disconnected.
controller board(CNMNT and CNVMNT).
A-Control Service Tool
Indication of the display
Alternately blinking display
Operation mode
Continued to the next page
Detailed
reference
page
P.32
P.33
(EA)
P.33
(Eb)
P.34
(EC)
P.39
P.39
P.39
(E8)
P.40
(E9)
P.38
P.39
P.38
P.39
P.40
P.41
P.40
P.41-
P.44