Appendix 1 Technical Data

Parameter
category
Operating temperature
Storage temperature
Relative humidity
Environmental
Altitude
Over-voltage level
Pollution level
Others
AC input system
Applicable power grid
Input voltage range
AC input
Input AC voltage frequency
Max input current
Power factor
Nominal outout voltage
Reted output voltage
Output DC voltage
Output DC current
DC output
Voltage set-point accuracy
Efficiency
Noise (peak-peak)
Weighted noise
AC input over-voltage alarm point
AC input over-voltage recovery
difference
AC input under-voltage alarm point
AC input under-voltage recovery
difference
AC input alarm
AC input over-voltage protection
and protection
point
AC input over-voltage protection
recovery difference
AC input under-voltage protection
point
AC input under-voltage protection
recovery difference
DC output over-voltage alarm point
DC output over-voltage recovery
difference
DC output under-voltage alarm point
DC output alarm
DC output under-voltage recovery
and protection
difference
DC output over-voltage protection
point
LLVD
BLVD
Load sharing
Rectifier
Derate by input (at 45° C)
NetSure 2100 A31-S1 Subrack Power System User Manual
Table 2 Technical data
Parameter
-5° C ~ 40° C
-40° C ~ 70° C
≤ 90%RH (30° C)
≤ 2000m (derating is necessary above 2,000m)
Level II
Level II
No conductive dust or erosive gases. No possibility of explosion
L+N+PE/220Vac
TN, TT
85Vac ~ 300Vac
45Hz ~ 65Hz
≤ 12.3A
≥ 0.99
-48Vdc
-53.5Vdc
-42.3Vdc ~ -57.6Vdc
0 ~ 34.4A (output voltage is -53.5V)
load current ≤ 20A, battery charge current ≤ 14.4A
≤ 1%
≥ 93.5%
≤ 200mV (0 ~ 20MHz)
≤ 2mV (300Hz ~ 3400Hz)
Default: 280Vac ± 5Vac, configurable through controller
Default: 270Vac ± 5Vac, 10Vac less than the AC input over-voltage
alarm point
Default: 180Vac ± 5Vac, configurable through controller
Default: 190Vac ± 5Vac, 10Vac higher than the AC input under-voltage
alarm point
Default 305Vac ± 5Vac, configurable through controller
Default: 295Vac ± 5Vac, 10Vac lower than the AC input over-voltage
protection point
Default: 80Vac ± 5Vac, configurable through controller
Default: 95Vac ± 5Vac, 10Vac higher than the AC input under-voltage
protection point
Default: -58.5Vdc ± 0.2Vdc, configurable through controller
Default: -58Vdc ± 0.2Vdc, 0.5Vdc lower than the DC output
over-voltage alarm point
Default: -45.0Vdc ± 0.2Vdc, configurable through controller
Default: -45.5Vdc ± 0.2Vdc, 0.5Vdc higher than the DC output
under-voltage alarm point
Default: -59.0Vdc ± 0.2Vdc, configurable through controller
Default: -44.0Vdc ± 0.2Vdc, configurable through controller
Default: -43.2Vdc ± 0.2Vdc, configurable through controller
The rectifiers can work in parallel and share the current. The unbalance
is better than ± 5% rated output current.
The rectifier can output power of 100% with input voltage of 176Vac;
The rectifier can output power of 750% with input voltage of 132Vac;
Rectifiers output 20% power with input voltage of 85Vac;
Rectifiers under-vlotage stop with input voltage of 80Vac
Appendix 1 Technical Data
Description
19