Note
If the controller does not detect the rectifier module, the rectifier information can not be queried.
The rectifier information includes rectifier No., output voltage, output current and start state.
At the MAINMENU screen (see Figure 4-7), press ▼ to select the 'Rect. Information' menu. Press ENT key to enter
the rectifier information screen, as shown in Figure 4-8.

4.4 Setting System Parameters

The 'Settings' screen has 14 parameters to be set: 'Batt Cap', 'BLVD Volt', 'FC Volt', 'BC Volt', 'Shunt Current', Shunt
Volt', 'ECO Enable', 'Clear', 'Address', 'Baud Rate', 'LLVD Enable', 'LLVD Volt', 'Relay 2' and 'Walk-in Time'. For 'Clear'
submenu, you can select 'History Alarm', 'Rect Lost', 'Communication Failure' and ' Testing abnormal' to clear
corresponding alarms.
Table 4-4 lists all the system parameter settings.
Batt Cap
BLVD Volt
FC Volt
BC Volt
Shunt Current
Shunt Volt
Address
Baud Rate
LLVD Enable
LLVD Volt
Relay 2
Walk-in Time
Figure 4-8 Rectifier information screen
Table 4-4 System parameter settings
Name
0/1 (Corresponding to disable/enable)
NetSure 2100 A31-S1 Subrack Power System User Manual
模块1:开
Rect.1 ON
53.5V 0.0A
Setting Range
Low
High
20
600
40
60
42
58
42
58
1
500
1
150
1 ~ 254
0/1/2/3
(Corresponding to
4800/9600/19200/38400)
40 ~ 60
0/1 (Corresponding to alarm
output/LLVD)
0, 8 ~ 128 (0 represents disable)
Chapter 4 Use Of Controller
Default
100
43.2
53.5
56.4
50
75
1
1 (Corresponding
to 9600)
0 (Disable)
44
0 (Alarm output)
0 (Disable)
13
Unit
Ah
V
V
V
A
mV
V
S