meanwhile, respectively fix the other two brackets after rotation to the middle of the subrack left and right side wall.
The position of the bracket is shown in Figure 2-2.
2. By referring to the dimension shown in Figure 2-1, mark the central points of the installation holes on the wall. Use
an electric drill (aiguille: Φ8) to dig holes (depth: 45mm) at the marked points. Clean the holes off dust. Put the four
expansion pipes (M6 × 65) into the holes and keep 20mm exposed.
3. As shown in Figure 2-2, use four groups of flat washer Ф6, spring washer Ф6 and nut M6 to fix the power system on
the wall.
4. After the installation, the power system should stand firmly no matter how it is shaken.
5. If rack mounting installation is used, firstly remove the three brackets, turn the bracket with the grounding screw to
make the grounding screw facing forward, and then fasten the bracket to the front of the subrack left side wall,
meanwhile, fix any one of the other two brackets after rotation to the front of the subrack right side wall (the rest
bracket is no need to be fixed). The position of the bracket is shown in Figure 2-2, use the fixing screws to fasten the
subrack power system to the rack through bracket.

2.4 Electrical Installation

All the cables entering or outgoing the power system must be put into the metal pipe for protection. The metal pipe
should be connected to the PE bar reliably. Plastic coated metal hoses are recommended.

2.4.1 Connecting Power Cable

Danger
Danger
1. Switch off all MCBs before the electrical connection.
2. Only the qualified personnel can do the mains cable connection.
3. Before electrical connection, make sure all the AC MCBs of the power system are switched off, the AC 230/400V 20A double
pole C type MCB is recommended.
4. There is a dangerous voltage in the primary circuit, disconnect the power supply before maintenance.
Connecting Earth Cable
Connect one end of the earth cable to the grounding terminal (see Figure 2-3), and solder the other end to the
grounding metal base outside the power system.
Wall
32
Figure 2-1 Installation dimension of cabinet base
Flat washer Ф6, spring washerФ6, nut M6 (4 group)
Figure 2-2 Fixing the power system