Total new design for the E-box. Optimizing design of the E-box, fresh air cooling down the temperature of the inverter module. 1.3.2 Adopting high performance main chip of NEC for the electronic control, higher reliability and operation speed. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 6
Different indoor units for choice. You can choose different indoor units appearance for your favorite. 1.5.2 Much more indoor units for free combination, meeting for different requirement such as office, house use, villa and etc. One or more indoor units’ connection combination for your choice. 1.5.3 GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A DC Inverter Multi-split Technical Manual General Information 4. External Appearance 4.1 Indoor Units Wall Mounted 155 Series Series 156 Series Ducted Units 4-way Cassette GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 12
R410A DC Inverter Multi-split Technical Manual General Information 4.2 Outdoor Units DC Dual-split DC Triple split DC Fourfold &Fivefold split GD Chigo Heating & Ventilation Equipment Co., Ltd.
The different style panels can satisfy your different requirements. All the units have various functions, such as the function of auto-restart, sleep mode are standard, golden fins and some filter for optional. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 18
3. Sound level: measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions. 4. The above data may be changed without notice for future improvement on quality and performance. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Indoor unit outline mm or 120 mm or more to wall more to wall Right rear side refrigerant pipe hole Left rear side refrigerant pipe hole Model A(mm) B(mm) ≤12000Btu/h 18000Btu/h 24000Btu/h 1200 GD Chigo Heating & Ventilation Equipment Co., Ltd.
Remark£ º OFF ON 1¡ ¢ M ake Memory short-circuit is a power outage memory otherwise for nothing 2¡ ¢ A ccording to the specific models to dial the code GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 22
R410A DC Inverter Multi-split Technical Manual Indoor Units CSG-18HVR1-A、CSG-24HVR1-A GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A DC Inverter Multi-split Technical Manual Indoor Units 9. Exploded View 150 series GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 35
Fixing tube panel Indoor motor Cross flow fan Motor cover assy Base assy Evaporator components Remote control battery Evaporator assy Chigo Elf general remote General manual plastic bag of export Evaporator damping rubber strip GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 36
R410A DC Inverter Multi-split Technical Manual Indoor Units 155 series GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 37
Fixing tube panel Indoor motor Cross flow fan Motor cover assy Base assy Evaporator components Remote control battery Evaporator assy Chigo Elf general remote General manual plastic bag of export Evaporator damping rubber strip GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 38
R410A DC Inverter Multi-split Technical Manual Indoor Units 156 series GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 39
Fixing tube panel Indoor motor Cross flow fan Motor cover assy Base assy Evaporator components Remote control battery Evaporator assy Chigo Elf general remote General manual plastic bag of export Evaporator damping rubber strip GD Chigo Heating & Ventilation Equipment Co., Ltd.
1.2 Adopting aviation centrifugal fans, and CFD technology design, increasing air-volume and decreasing noise level. 1.3 Three fan speed, meet different requirement. 1.4 High efficiency DC fan motor, low noise and more comfortable. Operate in low frequency and control indoor temperature precisely. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 43
R410A DC Inverter Multi-split Technical Manual Indoor Units 1.5 E-box is body-side design, convenient installation and maintenance. GD Chigo Heating & Ventilation Equipment Co., Ltd.
3. Sound level: measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions. 4. The above data may be changed without notice for future improvement on quality and performance. GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A DC Inverter Multi-split Technical Manual Indoor Units 4. Service Space Ensure enough space required for installation and maintenance. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Installation instruction for indoor The manual unit Insulating tube Ribbon Dome insulated tip X-type insulated tip Wire controller Connecting pipe of electronic expansion valve Connection wire for wired controller Blank valve bag GD Chigo Heating & Ventilation Equipment Co., Ltd.
1.2 Ultra-thin body design, the min. height is only 230mm, save installation space. 1.3 Built-in water pump ,water head up to 700 mm. 1.4 High efficiency DC fan motor, low noise and more comfortable. Operate in low frequency and control indoor temperature precisely. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 63
Indoor Units 1.5 Built in water tray , insulating foam coated by special plastic, preventing the leakage of the condensed water effectively 1.6 Standard for wireless controller; option for wired controller. Standard optional GD Chigo Heating & Ventilation Equipment Co., Ltd.
3. Sound level: measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions. 4. The above data may be changed without notice for future improvement on quality and performance. GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A DC Inverter Multi-split Technical Manual Indoor Units 4. Service Space Ensure enough space required for installation and maintenance. Model Machine body height(H) 7K/9K/12K/18K GD Chigo Heating & Ventilation Equipment Co., Ltd.
1.2 Soft start, the start current of the compressor is small and smooth. 1.3 Easy piping and wiring connection, no welding and only flare nut connection which makes the installation work easy and convenient. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 83
Max. pipe length (Between each IU and OU) Max. height difference 3×2.5 mm 3×2.5 mm Power wiring Connection wiring 4×1 mm 4×1 mm Signal wiring ˚C -15~48 -15~48 Ambient temperature 2×(10~15) 2×(12~18) Application area GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 84
Max. pipe length (Between each IU and OU) Max. height difference 3×4 mm 3×4 mm Power wiring Connection wiring 4×1 mm 4×1 mm Signal wiring ˚C -15~48 -15~48 Ambient temperature 3×(10~15) 3×(12~18) Application area GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 85
3. Sound level: measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions. 4. The above data may be changed without notice for future improvement on quality and performance. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Shutoff Valve EXVC temp sensor valve Condenser Coil temp Capillary Filter C 4-way sensor Liquid valve C valve Oil separator Gas valve A Gas valve B Shutoff Compressor valve Gas valve C GD Chigo Heating & Ventilation Equipment Co., Ltd.
Reactor EXVB IPM COMM EXVA DC FAN 4-WAY PFC Ctrl P-OUT N-OUT 16KBtu 18KBtu Factory default Example: POWER 4.7KW 5.3KW Caution 1: The Current Mutual inductor must be through with power cord. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 90
Reactor EXVB IPM COMM EXVA DC FAN 4-WAY PFC Ctrl P-OUT N-OUT Example: 21KBtu 27KBtu Factory default POWER 6.2KW 7.9KW Caution 1: The Current Mutual inductor must be through with power cord. GD Chigo Heating & Ventilation Equipment Co., Ltd.
T3 high temperature protection Display H4 after P6 protection for 3 Module protection times within 30 minutes Display H9 after P9 protection for 2 DC fan fault times within 10 minutes Anti-typhoon protection GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 112
MCE fault/sync/closed loop Zero speed protection Phase sequence error protection Protection when the speed change of two successive periods exceed 15Hz Protection of speed change(>15Hz) for the previous time and next time GD Chigo Heating & Ventilation Equipment Co., Ltd.
Take the air conditioner weight into account and select a place where noise and vibration will not be an issue. Select a place so that the warm air and noise from the air conditioner do not disturb neighbors. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Putting nut on Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal.(not possible to put them on after flaring work). GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 116
Quintuple split indoor and outdoor units Difference in height between Max. 5m indoor units 3.3 Connection pipe diameter: Indoor unit Liquid Accessories φ6.35 φ9.52 7K/9K/12K φ6.35 φ12.7 Adapter φ9.52 φ15.88 Adapter component GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 117
6.35mm to 9.52mm,and connector diameter of indoor unit is 9.52mm. (3)The adapter component is included inside the accessory of indoor uint. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Caution in handling the packed valve ● Open the valve stem until it hits against the stopper. Do not try to open it further. ● Securely tighten the valve stem cap with a spanner or the like. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 119
7. Remove the charge hose from the Low pressure charge hose. 8. Fully open the packed valve stems B and A. 9. Securely tighten the cap of the packed valve. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 120
R410A DC Inverter Multi-split Technical Manual Control System Vacuum 1.For one drive two unit: Vacuum for two indoor units separately. 2.For one drive three unit: Vacuum for three indoor units separately. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 121
Vacuum from the main valve, no need vacuum for each indoor unit; b. Make sure main valve close before vacuum, then open all small valves for indoor units , keep the small valve close if there is no indoor unit. GD Chigo Heating & Ventilation Equipment Co., Ltd.
If bubbles come out, the pipes have leakage. ● Leak detector Use the leak detector to check for leakage. Caution: A,B,C,D and E are packed valve of outdoor unit. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 123
Note: The illustration is for explanation purpose only. The actual order of A,B,C,D and E on the machine may be slightly different from the unit you purchased. The actual shape shall prevail. GD Chigo Heating & Ventilation Equipment Co., Ltd.
The dimension of drainpipe can’t less than the connecting dimension of indoor drainpipe. Heat-insulation should be done well to prevent condensation. Indoor units with different drainage type can’t share one convergent drainpipe. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Insulation for non-jointing parts and non-connection parts. wrong Right Gas pipe and liquid pipe should not be put Insulate the gas pipe (cooling only) Insulate the gas pipe and liquid pipe together to insulate GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 126
Insulate for the jointing area, expanding area and the flange area should be done after checking leakage of the pipes Make sure there’s no clearance in the joining part of the accessorial insulation material and local preparative insulation material. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 127
The gas and liquid pipe should be heat insulated individually, the connecting part should be heat insulated individually. Use the attached heat-insulation material to insulate the pipe connections (pipes’ tie-in, expand nut ) of the indoor unit. GD Chigo Heating & Ventilation Equipment Co., Ltd.
R410A DC Inverter Multi-split Technical Manual Control System Part 5. Test Running 1. Dialing setting of main control board Switch No. Dialing Illustration GD Chigo Heating & Ventilation Equipment Co., Ltd.
Last fault protection code (no fault display -) Control parameters (only for use of Capacity need of indoor unit "B" development personnel),display "- -" Capacity need of indoor unit "C" Control parameters (only for use of GD Chigo Heating & Ventilation Equipment Co., Ltd.
7. Check if the power supply phase sequence of the outdoor unit is correct. 8. Check if all dialing switches of the indoor and outdoor units are set according to the technical requirements of the product. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Calculate the indoor volume (B [m ]) (by the minimum volume) c) Calculate the refrigerant concentration. [] ≤ ∶ 0.3[/ [ GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 132
R410A DC Inverter Multi-split Technical Manual Control System 5. Measures against exceeding the critical concentration a) To reduce the refrigerant concentration below the critical concentration, install a mechanical ventilation device (for frequent ventilation). GD Chigo Heating & Ventilation Equipment Co., Ltd.
Press the key and the remote control will switch circularly in the order: ON→OFF→ON. When it is powered on at first from off state to on state, the default setting of work condition is ( The set temperature is 25℃ and the GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 134
Pressing MODE key can’t cancel timing in timing mode which will send out the order of timing time by pressing other key. GD Chigo Heating & Ventilation Equipment Co., Ltd.
Page 135
CLEAN →cancel CLEAN→ CLEAN; when you stop the unit and turn on the purification switch, except the wind, the stable swing and air door swing speed aren’t adjusted. GD Chigo Heating & Ventilation Equipment Co., Ltd.