Setting the Keyboard Disable Function
GB
IMPORTANT: See Security Settings on page 10.
This feature allows the building
owner to disable all programming
functions and to limit the degree of
temperature override that the user
can select to ± 2°C.
The Keyboard Disable Function is
pre-set to OFF. If you would like to
disable the keyboard use the + or
- buttons until your preference is
selected.
When the keyboard is disabled the use of the
temperature override buttons is limited to ± 2°C.
Press the PROG button to advance to the next setting option.
Setting Compressor Time Delay
The compressor time delay feature is only active if DIL switch 2
(compressor time delay) is set to enabled and is only available
on models with cooling output.
This feature allows the installer to
select the minimum compressor off
times. The compressor time delay
is preset to 2 minutes minimum off
time. Use the + or - buttons until
your preference is selected. The
options are 1, 2, 3, 4 or 5 minutes
minimum off time.
Press the PROG button to advance to the next setting option.
8
(option 1)
+
-
or
or
(option 2)
+
-
or