Page 3
Minimum Gas Pipe Sizing Guide For Black Iron pipe Refer to Sizing charts for a complete system design Mascot Models Output btu Branch Gas Line HT 330/1.330 126,376 3/4" HT 1.450 167,262 1" HT 1.650 241,600 1" Linear Feet Gas Pipe BTUH in Thousands 50 ft 75 ft...
Page 4
HT 330 VALVE PLACEMENTS Be sure to use the supplied fiber gaskets DO NOT OVER TIGHTEN FITTINGS! Boiler Supply T&P Relief Valve Valve Increase from This valve is 3/4” to 1-1/4” vertical 3/4” Condensate Boiler Return Drain Valve Increase from w/Screen 5/8”...
Page 5
HT 1.330 VALVE PLACEMENTS Be sure to use the supplied fiber gaskets DO NOT OVER TIGHTEN FITTINGS! Water Feed Inlet Valve 1/2” with check- valve Boiler Supply T&P Relief Valve Valve Increase from This valve is 3/4” to 1-1/4” vertical 3/4” Boiler Return Condensate Gas Supply...
Page 10
Water Pipe Sizing Guide Refer to Sizing Charts for a complete system design Water - BTU formula: GPM X Temp. Change X 500= BTUH Maximum Flow BTUH per 10º F BTUH per 20º F BTUH per 40º F BTUH per 60º F BTUH per 80º...