Power Supply Wiring - Mitsubishi Electric Fresh Master GUF-50RD3 Installation Instructions Manual

City multi series
Hide thumbs Also See for Fresh Master GUF-50RD3:
Table of Contents

Advertisement

8.4. Power supply wiring

2
Power cable size: 1.5 mm
or more
Total operating current
Over current
be less than 16 A
protection 16 A
Switch 16 A
[Selecting non-fuse breaker (NF) or earth leakage breaker (NV)]
To select NF or NV instead of a combination of Class B fuse with switch,
use the following:
In the case of Class B fuse rated 15 A or 20 A,
NF model name (MITSUBISHI): NF30-CS (15 A) (20 A)
NV model name (MITSUBISHI): NV30-CA (15 A) (20 A)
Use an earth leakage breaker with a sensitivity of less than 30 mA 0.1
sec.
Overcurrent
protection 16 A
Switch 16 A
Caution:
Do not use anything other than the correct capacity breaker and
fuse. Using fuse, wire or copper wire with too large capacity may
cause a risk of malfunction or fire.
8.5. Connecting the Remote controller,
the Fresh Master and outdoor
transmission cables
(The Remote controller is optionally available.)
Connect Fresh Master TM2 and outdoor unit TB3. (Non-polarized
2-wire)
The "S" on Fresh Master TM2 is a shielding wire connection. For
specifications about the connecting cables, refer to the outdoor unit
installation manual.
Install the Remote controller following the manual supplied with the
Remote controller.
[For using the ME Remote controller]
Connect the "A" and "B" on Fresh Master TM2 to the Remote control-
ler. (Non-polarized 2-wire) Connect the Remote controller's transmis-
sion cable within 200 m. If the distance is more than 10 m, use a 1.25
mm
2
to 2.0 mm
2
cable.
[For using the MA Remote controller]
Connect the "1" and "2" on Fresh Master TM2 to the Remote control-
ler. (Non-polarized 2-wire) Connect the Remote controller's transmis-
sion cable within 200 m.
Terminal block for the
Fresh Master
transmission cable
S B A 2 1
TM2
(Fresh Master)
TB3
S B A 2 1
ME Remote
Terminal block for outdoor
controller
transmission cable
(PAR-F27MEA)
Pull box
Fresh Master
Fresh Master
S B A 2 1
TM2
(after Fresh Master)
MA Remote controller
(PAR-20MAA)
24 to 30 V DC between M1 and M2
Longest wiring length (L1+L2+L4 or L1+L3): less than 200 m
Longest wiring length (L2+L3+L4): less than 500 m
Length between the Fresh Master and the Remote controller (R): within
10 m
Notes:
*1 Put the transmission cable earth via the outdoor unit's earth
terminal
to the ground.
*2 If the Remote controller cable exceeds 10 m, use a 1.25 mm
2.0 mm
2
cable over the exceeded portion, and add that ex-
ceeded portion to within 200 m.
*3 The BC controller is required only for simultaneous cooling
and heating series R2.
[Constraints on transmission cable]
G
*1
H
I
*3
J
L1
G Outdoor unit
H Earth
I BC controller
J Fresh Master
K Remote controller
L Non-polarized 2-wire
J
J
L2
K
K
L4
J
J
R
K
L
L3
K
K
15
2
to
*2