Appendices; Appendix A: Agency Approvals - Liebert MPX User Manual

Rack power distribution unit
Hide thumbs Also See for MPX:
Table of Contents

Advertisement

APPENDICES

Appendix A: Agency Approvals

The MPX units comply with the following North American and European standards.
A.1 North American units
The 120 V and 240 V single-phase and 120/208-240 V three-phase North American MPX™ units have the
following agency approvals: 
UL 60950-1 Standard for Safety: Information Technology Equipment - Safety - Part 1: General
Requirements
CSA C22.2 No. 60950-1: Information Technology Equipment - Safety, Part 1 General Equipment
- Safety - Part 1: Requirements
FCC, Title 47, Part 15 Subpart B for Class A operation as defined by ANSI Standard C63.4.
ISTA Procedure 1A and 2A
RoHS Compliant
A.2 European units
The 230 V single-phase and 400 V three-phase European MPX units have the following agency
approvals: 
CE Compliant according to:
Low-Voltage Directive 2014/35/EU
Electromagnetic - Compatibility Directive 2014/30/EU (EMD)
RoHS Directive 2011/65/EC
WEE Directive 2012/19/EU
ISTA Procedure 1 A and 2A
ROHS and WEEE Compliant, Basic Test for Purchased Products according to International
Safe Transit Association
A.1 Electrical and Environmental Specifications
SPECIFICATION
Power Consumption
Maximum Ratings
Insulation
Electric Strength
Overcurrent Protection
Operating Temperature
Humidity
Altitude
Storage Temperature Range
Vertiv | Liebert® MPX™ Rack Power Distribution Unit Installer/User Guide |
PARAMETER
22 W maximum per fully configured 42U model (RPC, RPC BDM, MPX PEM, 6xBRM-R): 3 W per
RPC; 0.4 W per module + 0.4 W per open control (energized condition)
Maximum 240/415 V, 50/60 Hz, 63 A; dependent on MPX PEM selection
Class I, Basic Earthed SELV
2200 VDC
UL489 Overcurrent Circuit Breaker per Branch, 20 A, 5000 A A.I.C
Up to 140° F (60° C)
5-95%, non-condensing
6560 ft (2000 m) without derating
-13° F to 185° F (-25° C to 85° C)
45