62
Read the measured and calculated
function values
6HUYLFH5HSRUW
)XQFWLRQV
'LIIHUHQWLDO
'LII&RP

6FUROO WKH OLVW WR YLHZ HDFK YDOXH
Use the /HIW and/or 5LJKW arrow buttons to scroll between values.
 NELW GDWD FRPPXQLFDWLRQ YDOXHV
Path in local HMI: ServiceReport/Functions/Differential/DiffCom
7DEOH  5HPRWH WHUPLQDO FRPPXQLFDWLRQ
9LHZHG GDWD GHIDXOW ODEHOV XVHG GDWD LV
H[DPSOH YDOXHV
TransmDelay=
0.345 ms
NoOfShlnterr=
199
NoOfMedlnterr=
12
NoOfLonglnterr=
2
CommStatus=
OK
NoOfTXD=
37 %
NoOfRXD=
41 %
SyncError=
5 us
9LHZ WKH VHUYLFH UHSRUW
&RPPXQLFDWLRQ YDOXHV
One half of measured loop time delay in
transmission of communication telegram
Recorded number of short interruptions in
communication to the remote terminal (20 -
50 ms)
Recorded number of medium interruptions in
communication to the remote terminal (50 -
200 ms)
Recorded number of long interruptions in
communication to the remote terminal
>200ms
Status of communication link
Percentage of theoretically possible transmit-
ted telegrams
Percentage of received transmitted telegrams
Synchronization error between two terminals