ABB REL 561*2.5 Operator's Manual page 68

Protectit line differential and distance protection terminal
Table of Contents

Advertisement


Read the measured and calculated
function values
7DEOH  &DOFXODWHG GLIIHUHQWLDO YDOXHV
9LHZHG GDWD GHIDXOW ODEHOV XVHG GDWD LV
H[DPSOH YDOXHV
IDiffL1=
0.003 A
IBiasL1=
0.734 A
IDiffL2=
0.004 A
IBiasL2=
0.733 A
IDiffL3=
0.002 A
IBiasL3=
0.735 A
9LHZ WKH GLIIHUHQWLDO FRPPXQLFDWLRQ YDOXHV
This procedure describes how to read differential communication values.
3URFHGXUH

9LHZ WKH OLVW RI DYDLODEOH FRPPXQLFDWLRQ GDWD
Navigate the menus to:
9LHZ WKH VHUYLFH UHSRUW
'LIIHUHQWLDO YDOXH
Measured actual value of differential current in
phase L1
The highest value of Bias currents in phase L1
or 1/2 of Bias current in L2 or 1/2 of Bias current
in L3
max [(I
L1 or 0,5xI
L2 or 0,5I
bias
bias
Measured actual value of differential current in
phase L2
The highest value of Bias currents in phase L2
or 1/2 of Bias current in L1 or 1/2 of Bias current
in L3
max [(I
L2 or 0,5xI
L1 or 0,5I
bias
bias
Measured actual value of differential current in
phase L3
The highest value of Bias currents in phase L3
or 1/2 of Bias current in L2 or 1/2 of Bias current
in L1
max [(I
L3 or 0,5xI
L2 or 0,5I
bias
bias
&KDSWHU 
L3)]
bias
L3)]
bias
L1)]
bias
61