Toshiba RAV-SM407MUT-E Installation Manual page 25

Hide thumbs Also See for RAV-SM407MUT-E:
Table of Contents

Advertisement

4
Cleaning with water or vacuum cleaner.
• If dirt is heavy, clean the air filter using tepid
water with a neutral detergent or just water.
• After cleaning with water, dry the air filter
sufficiently in a shaded place.
5
Mount the air filter.
6
Close the air intake grille.
• Check that the fall-preventive strap of the air
intake grille is attached to the panel.
• In inverse process of 1, firmly attach the hook,
fixing bracket and fixing screw.
7
Turn on the circuit breaker, then push the
button on the remote controller to
start the operation.
8
After cleaning, push
.
display disappears.
CAUTION
CAUTION
• Do not start the air conditioner while leaving air filter
removed.
• Push the filter reset button. (
indication will be turn
off.)
47-EN
Hook
▼ Periodic Maintenance
• For environmental conservation, it is strongly recommended that the indoor and outdoor units of the air
conditioner in use be cleaned and maintained regularly to ensure efficient operation of the air conditioner.
When the air conditioner is operated for a long time, periodic maintenance (once a year) is recommended.
Furthermore, regularly check the outdoor unit for rust and scratches, and remove them or apply rustproof
treatment, if necessary.
As a general rule, when an indoor unit is operated for 8 hours or more daily, clean the indoor unit and outdoor
unit at least once every 3 months. Ask a professional for this cleaning / maintenance work.
Such maintenance can extend the life of the product though it involves the owner's expense.
Failure to clean the indoor and outdoor units regularly will result in poor performance, freezing, water leakage,
and even compressor failure.
Inspection before maintenance
Following inspection must be carried out by a qualified installer or qualified service person.
Parts
Open the air intake grille to remove the bell mouth and the fan, and then check the heat exchanger
Heat exchanger*
if there is any clogging or damages.
Fan motor
Check if any abnormal noise can be heard.
Fan
Open the air intake grille and check the fan if there are any waggles, damages or adhesive dust.
Filter
Open the air intake grille and check if there are any stains or breaks on the filter.
Remove the panel, the bell mouth and the drain pan, and then check if there is any clogging,
Drain pan*
abnormal smell or drain water pollution.
* Refer to the Service Manual for how to remove.
▼ Maintenance List
Part
Unit
Heat exchanger
Indoor / outdoor
Fan motor
Indoor / outdoor
Filter
Indoor
Fan
Indoor
Air intake / discharge
Indoor / outdoor
grilles
Drain pan
Indoor
Ornamental panel,
Indoor
louvres
Exterior
Outdoor
– 24 –
Inspection method
Check (visual / auditory)
Maintenance
Wash the heat exchanger when it is
Dust / dirt clogging, scratches
clogged.
Take appropriate measures when
Sound
abnormal sound is generated.
• Wash the filter with water when it is
contaminated.
Dust / dirt, breakage
• Replace it when it is damaged.
• Vibration, balance
• Replace the fan when vibration or
balance is terrible.
• Dust / dirt, appearance
• Brush or wash the fan when it is
contaminated.
Fix or replace them when they are
Dust / dirt, scratches
deformed or damaged.
Dust / dirt clogging, drain
Clean the drain pan and check the
contamination
downward slope for smooth drainage.
Wash them when they are contaminated
Dust / dirt, scratches
or apply repair coating.
• Rust, peeling of insulator
Apply repair coating.
• Peeling / lift of coat
48-EN