(2) Applied cable size
Select the recommended cable size to ensure that a voltage drop will be 2% max.
If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor
torque to decrease especially at the output of a low frequency.
The following table indicates a selection example for the wiring length of 20m (65.62feet).
600V class
Terminal
Applicable
Screw
Inverter Type
Size
FR-A760-00017-NA
M4
FR-A760-00040-NA
M4
FR-A760-00061-NA
M4
FR-A760-00120-NA
M4
FR-A760-00220-NA
M5
FR-A760-00330-NA
M6
FR-A760-00550-NA
M8
FR-A760-00840-NA
M8
*1
The cables used should be 75°C (167°F) copper cables.
*2
The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, a screw for earthing (grounding), and P/+ for option connection.
The line voltage drop can be calculated by the following formula:
3 × wire resistance[mΩ/m] × wiring distance[m] × current[A]
line voltage drop [V]=
Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque
reduction) in the low speed range.
CAUTION
· Tighten the terminal screw to the specified torque.
A screw that has been tighten too loosely can cause a short circuit or malfunction.
A screw that has been tighten too tightly can cause a short circuit or malfunction due to the unit breakage.
· Use crimping terminals with insulation sleeve to wire the power supply and motor.
Crimping Terminal
Tightening
Torque
R/L1,
N·m
S/L2,
*2
U, V, W
T/L3
P/+, P1
1.5
2-4
2-4
1.5
2-4
2-4
1.5
2-4
2-4
1.5
3.5-4
2-4
2.5
5.5-5
5.5-5
4.4
14-6
14-6
7.8
22-8
22-8
7.8
38-8
38-8
mm
R/L1,
Earth
S/L2,
(Ground)
U, V, W
T/L3,
Cable
P/+, P1
2-4
2
2-4
2
2-4
2
3.5-4
3.5
5.5-4
5.5
5.5
14-6
14
22-8
22
22-8
38
1000
Cable Sizes
*1
2
R/L1,
Earth
S/L2,
(Ground)
T/L3,
Cable
P/+, P1
2
2
14
2
2
14
2
2
14
2
3.5
12
5.5
10
14
14
6
22
22
4
38
22
2
WIRING
AWG
Earth
U, V, W
(Ground)
Cable
14
14
14
14
14
14
14
12
10
10
6
6
4
4
2
4
8