Kilograms Weight 2.1.9 The same DYN1-1065X or DYN1-1068X Series can be Pounds 11.0 used on a DYNA 8000, DYNA 8200 or DYNA 8400 actuator. Maximum Amperes @ Stall 12.5 Current @ 12 VDC The DYN1-1068X governor control box provides a wider range Nominal Steady State Amperes of adjustment than the DYN1-1065X.
Page 4
2.2.11 AVAILABLE DYNA 8000 HAZARDOUS DUTY 2.2.7 AVAILABLE DYNA 8000 ACTUATOR MODELS ACTUATOR MODELS WITH CLOCKWISE OUTPUT SHAFT WITH CLOCKWISE OUTPUT SHAFT ROTATION ROTATION (Standard Mounted Units) (Standard Mounted Units) • DYNC-11020-400-0-12 Standard Clockwise • DYNC-11020-000-0-12 Standard Clockwise DYNC-11020-400-0-24 Output Shaft Rotation DYNC-11020-000-0-24 Output Shaft Rotation •...
2.4.7 AVAILABLE DYNA 8400 ACTUATOR MODELS Joules 2.85 Work WITH TERMINAL STRIP CONNECTION Foot-Pounds 2.10 Newton-Meters 4.07 Torque • DYNC-14800-000-0-24 Through Output Shaft Making Pound-Foot 3.00 Available CW and CCW Output Output Rotary 45° Kilograms Weight 2.4.8 AVAILABLE DYNA 8400 ACTUATOR MODELS Pounds 18.5 WITH 2-PIN MS SCREW ON CONNECTOR...
3.7 REMOTE SPEED ADJUSTMENT 3.5 ISOCHRONOUS OPERATION Isochronous operation is obtained by setting droop potentiom- An optional remote speed selector (DYNS-10000) is available eter fully counterclockwise. The DYNA governor is all electric, for adjusting engine RPM from up to 90 meters (300 ft.) from the and it is normally operated in the isochronous mode;...
Page 7
2 Pin Connector No.MS3106A 10-SL-4S Magnetic Pickup has 5/8-18 Threads Jam Nut Speed Sensor Engine Housing Ring Gear .37 ± .127 mm [.015 ± .005] INSTALLATION OF MAGNETIC PICKUP 4.1.4 Mount the controller in the control panel. 4.1.5 Connect the wiring as shown in section 4.3 or according to your particular wiring diagram. 4.2 TYPICAL LINKAGE ARRANGEMENTS FOR THE ACTUATOR AND FUEL SYSTEM 4.2.1 ROTARY ACTUATOR TO ROTARY FUEL PUMP Rod End...
Page 8
4.3 TYPICAL WIRING DIAGRAM & CONTROLLER INSTALLATION DIMENSIONS DIMENSIONS -- DYNA 8000 CONTROLLER -- DYN1 1065X and DYN1 1068X Dimensions are in mm except as otherwise noted. Dimensions in [ ] are in inches. Chassis ground screw Cable A -- DYNK-44-XX (specify length) (90°...
5. CALIBRATION OF DYNA 8000 SERIES CONTROLLER — DYN1-1065X Input Signal Input Signal Frequency Frequency Maximum Part Number Maximum Part Number DYN1-10652-000-0-12/24 DYN1-10654-000-0-12/24 250 to 1200 Hz 2500 to 5000 Hz DYN1-10652-001-0-12/24* DYN1-10654-001-0-12/24* DYN1-10656-000-0-12/24 DYN1-10653-000-0-12/24 1200 to 2500 Hz 5000 to 9000 Hz...
Page 10
"On" "Off" 5.3.2 Two actuator selections, so the same controller can be used on the DYNA 8000, DYNA 8200 or DYNA 8400 actuator.* • Set S2 to the OFF position when using a DYNA 8000 Answer: The drawings above should clarify any confusion actuator.
6.4) Set switch S2 in the "OFF" position for actuator overshoot. If there is a small hunt at steady state, slightly turn DYNA 8000 or in the "ON" position for DYNA 8200 and 8400. the "I" potentiometer counterclockwise until stable. In some cases, 2 to 3 Hz overshoot may be acceptable.
Page 12
Switch S2 selects the point at which actuator coil current level causes the integrator limit to be actuated. This level is nominally 6.3 amperes for the DYNA 8000 and 7.3 amperes for the DYNA 8200 and 8400 actuator. 6.6 PROPER PROCEDURES FOR SETTING SWITCHES S1...
7. DYNA 8000 SERIES TROUBLESHOOTING CHART 7.1 PROBLEM: GOVERNOR IS COMPLETELY DEAD AND ACTUATOR LEVER STAYS AT MINIMUM POSITION WHEN POWER IS APPLIED TO GOVERNOR. Means of Detection Corrective Action 7.1.1 Check battery voltage at terminals 1 and 2 on Check battery connections and contacts for turning power controller.
Page 14
7.2 PROBLEM: ACTUATOR GOES TO FULL STROKE WHEN DC POWER IS TURNED ON (ENGINE IS NOT OPERATING). Means of Detection Corrective Action 7.2.1 Check magnetic pickup leads for proper Verify and correct wiring as necessary. shielded wire or open shield. 7.2.2 Be sure there is no jumper between terminals Verify and correct wiring as necessary.
7.5 PROBLEM: SLOW, SMALL AMPLITUDE HUNTING OF SPEED OR FREQUENCY Means of Detection Corrective Action Correct Linkage. 7.5.1 Sticking or very loose linkage. 7.6 PROBLEM: FAST OSCILLATION OF GOVERNOR LINKAGE Means of Detection Corrective Action 7.6.1 Verify calibration settings of the controller. Readjust settings as necessary.
Page 17
DYNC-14800-000 TERMINAL STRIP CONNECTION DYNC-14801-000 2-PIN MS CONNECTOR CONNECTION DYNC-11020-401 UL APPROVAL, HAZARDOUS DUTY, CLASS 1, DIVISION 2, GROUP D CLOCKWISE UNIT...
Page 18
Facsimile (815) 877-0150 Loves Park, IL 61132-2940 www.dynaproducts.com United States of America In Europe contact: Barber-Colman GmbH Am Neuen Rheinhafen 4, D-67346 Speyer, Germany Telephone (49) 6232 29903, Facsimile (49) 6232 299155 In Japan contact: Ranco Japan Ltd. Shiozaki Bldg. 7-1, 2-chome, Hirakawa-Cho, Chiyoda-Ku...