Table B2. Veris Multipliers for Integer Registers 40001 - 40027
Address
Units
40001
KWH LSB
40002
KWH MSB
40003
KW
40004
KVAR
40005
KVA
40006
aPF
40007
VOLTS L-L
40008
VOLTS L-L
40009
AMPS
40010
KW L1
40011
KW L2
40012
KW L3
40013
aPF L1
40014
aPF L2
40015
aPF L3
40016
VOLTS L1-L2
40017
VOLTS L2-L3
40018
VOLTS L3-L1
40019
VOLTS L1-N
40020
VOLTS L2-N
40021
VOLTS L3-N
40022
AMPS L1
40023
AMPS L2
40024
AMPS L3
40025
KW
40026
KW
40027
KW
Per the Veris implementation, to obtain true engineering units, the values returned from the registers in Table
B1 must be multiplied by the scaling value found in Table B2. For example, if the PowerScout
connected to it, then to get system reactive power (kVARs) multiply the value returned from reading register
40004 by 0.004.
Shop for Dent products online at:
≤100A
101 - 400A
7.8125exp-3
0.03125
512
2048
0.004
0.016
0.004
0.016
0.004
0.016
3.0518exp-5
3.0518exp-5
0.03125
0.03125
0.015625
0.015625
3.9063exp-3
0.015625
0.001
0.004
0.001
0.004
0.001
0.004
3.0518exp-5
3.0518exp-5
3.0518exp-5
3.0518exp-5
3.0518exp-5
3.0518exp-5
0.03125
0.03125
0.03125
0.03125
0.03125
0.03125
0.015625
0.015625
0.015625
0.015625
0.015625
0.015625
3.9063exp-3
0.015625
3.9063exp-3
0.015625
3.9063exp-3
0.015625
0.004
0.016
0.004
0.016
0.004
0.016
22
PowerMeterStore
www.
401 – 800A
801 - 1600A
0.0625
.125
4096
8192
0.032
0.064
0.032
0.064
0.032
0.064
3.0518exp-5
3.0518exp-5
0.03125
0.03125
0.015625
0.015625
0.03125
0.0625
0.008
0.016
0.008
0.016
0.008
0.016
3.0518exp-5
3.0518exp-5
3.0518exp-5
3.0518exp-5
3.0518exp-5
3.0518exp-5
0.03125
0.03125
0.03125
0.03125
0.03125
0.03125
0.015625
0.015625
0.015625
0.015625
0.015625
0.015625
0.03125
0.0625
0.03125
0.0625
0.03125
0.0625
0.032
0.064
0.032
0.064
0.032
0.064
.com
1601 -
32,000A
0.25
16384
0.128
0.128
0.128
3.0518exp-5
0.03125
0.015625
0.125
0.032
0.032
0.032
3.0518exp-5
3.0518exp-5
3.0518exp-5
0.03125
0.03125
0.03125
0.015625
0.015625
0.015625
0.125
0.125
0.125
0.128
0.128
0.128
has 100A CTs